Worked example
Example: Axial main fan, mine R 0.06 N s2/m8. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Fan curve point 1: flow | 100.00 m³/s |
| Point 1: fan pressure | 1,850.0 Pa |
| Point 2: flow | 150.00 m³/s |
| Point 2: fan pressure | 1,600.0 Pa |
| Point 3: flow | 200.00 m³/s |
| Point 3: fan pressure | 1,100.0 Pa |
| Mine resistance (N·s²/m⁸) | 0.060000 - |
| Natural pressure assisting the fan (negative opposing) | 0 Pa |
| Fan efficiency | 75.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Operating air flow | 159.42 m³/s |
| Fan pressure | 1,524.9 Pa |
| Air power | 243.10 kW |
| Fan shaft power | 324.14 kW |
| Mine pressure drop | 1,524.9 Pa |
Open this example in the calculator and change any input.
Formula
\(p_f(Q) = c_0 + c_1 Q + c_2 Q^2 = R Q^2 - NVP, \quad P_s = \frac{p_f Q}{\eta}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_1\) | Fan curve point 1: flow | m³/s |
| \(p_1\) | Point 1: fan pressure | Pa |
| \(Q_2\) | Point 2: flow | m³/s |
| \(p_2\) | Point 2: fan pressure | Pa |
| \(Q_3\) | Point 3: flow | m³/s |
| \(p_3\) | Point 3: fan pressure | Pa |
| \(R\) | Mine resistance (N·s²/m⁸) | - |
| \(NVP\) | Natural pressure assisting the fan (negative opposing) | Pa |
| \(\eta\) | Fan efficiency | - |
| \(Q\) | Operating air flow | m³/s |
| \(p_f\) | Fan pressure | Pa |
| \(p_f Q\) | Air power | W |
| \(P_s\) | Fan shaft power | W |
| \(RQ^2\) | Mine pressure drop | Pa |
Method and standards
Intersection of fan and mine characteristics.
Where it is used
- Main fan selection and blade-angle setting.
- Predicting the effect of new workings.
Common mistakes
- Using total and static fan pressures inconsistently.
- Extrapolating the fan curve.
Assumptions and limits
- Quadratic fan curve between the points.
References
- Peele (ed.)
- Mining Engineers' Handbook
- 3rd ed. (Wiley, 1941)
- sec. 14
- Mine Ventilation
- art. 15 (pressure-quantity characteristics of fans and mines) and art. 12 (natural draft)
Questions and answers
Why does natural pressure shift the duty?
Assisting natural draft lowers the pressure the fan must supply, so it delivers more air; opposing draft does the reverse.
What if the resistance rises?
The mine curve steepens and the point moves left to less air and more pressure, possibly into the fan's stall region.
What do the defaults represent?
An axial main fan giving 1,850, 1,600 and 1,100 Pa at 100, 150 and 200 m³/s on a mine of 0.06 N·s²/m⁸, 75 % efficient.