Pipe Loop Balancing by Hardy Cross (One Loop)

Corrected flows in a four-pipe loop by the Hardy Cross method from pipe resistances and assumed flows, with the loop correction and head loss.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalChemical and fertiliserPulp and paper

Inputs

Examples: Four-pipe loop, Hazen–WilliamsDarcy loop n = 2

Results

Assumed flows must satisfy continuity at every junction; the correction keeps it. Iterated to convergence, so the head losses around the loop sum to zero. Resistances from Hazen–Williams r = 10.67L/(C^1.852D^4.87) or Darcy r = 8fL/(gπ²D⁵).

Balanced flow pipe 10.055097m³/s
Balanced flow pipe 20.025097m³/s
Balanced flow pipe 3-0.044903m³/s
Balanced flow pipe 4-0.024903m³/s
Total loop correction-0.004903m³/s
Head loss in pipe 12.3310m

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Four-pipe loop, Hazen–Williams. The inputs, in the units selected above:

InputValue
Head-loss exponent (1.852 Hazen–Williams, 2 Darcy)1.8520 -
Resistance pipe 1 (h = rQ^n, SI)500.00 -
Assumed flow pipe 1 (clockwise +)0.060000 m³/s
Resistance pipe 2800.00 -
Assumed flow pipe 20.030000 m³/s
Resistance pipe 3600.00 -
Assumed flow pipe 3-0.040000 m³/s
Resistance pipe 41,200.0 -
Assumed flow pipe 4-0.020000 m³/s

Applying the formula below gives:

ResultValue
Balanced flow pipe 10.055097 m³/s
Balanced flow pipe 20.025097 m³/s
Balanced flow pipe 3-0.044903 m³/s
Balanced flow pipe 4-0.024903 m³/s
Total loop correction-0.004903 m³/s
Head loss in pipe 12.3310 m

Open this example in the calculator and change any input.

Formula

\(\Delta Q = -\frac{\sum rQ|Q|^{n - 1}}{n\sum r|Q|^{n - 1}}\)

Variables

Symbol Meaning SI unit
\(n\) Head-loss exponent (1.852 Hazen–Williams, 2 Darcy) -
\(r_1\) Resistance pipe 1 (h = rQ^n, SI) -
\(Q_1\) Assumed flow pipe 1 (clockwise +) m³/s
\(r_2\) Resistance pipe 2 -
\(Q_2\) Assumed flow pipe 2 m³/s
\(r_3\) Resistance pipe 3 -
\(Q_3\) Assumed flow pipe 3 m³/s
\(r_4\) Resistance pipe 4 -
\(Q_4\) Assumed flow pipe 4 m³/s
\(Q_1'\) Balanced flow pipe 1 m³/s
\(Q_2'\) Balanced flow pipe 2 m³/s
\(Q_3'\) Balanced flow pipe 3 m³/s
\(Q_4'\) Balanced flow pipe 4 m³/s
\(\Delta Q\) Total loop correction m³/s
\(h_1\) Head loss in pipe 1 m

Method and standards

Hardy Cross correction.

Where it is used

  • Plant water and fire-water ring mains.
  • Teaching network analysis.

Common mistakes

  • Assumed flows violating continuity.
  • Inconsistent sign convention.

Assumptions and limits

  • Single loop; fixed resistances.
  • Resistances r are in SI (h in m, Q in m³/s, h = rQⁿ); flows may be entered in any flow unit and are converted to m³/s.
  • The iteration must converge (|ΔQ| below 10⁻¹² of the flows) or the page reports failure.

References

  • Hardy Cross (1936) method of balancing heads (Streeter and Wylie, Fluid Mechanics, ch. 11)

Questions and answers

Why must head losses sum to zero?

Going round a loop you return to the same point, so the net change in head is zero.

Why do assumed flows need continuity?

The loop correction adds the same ΔQ to every pipe, which keeps junction balances but cannot fix them.

What do the defaults represent?

A four-pipe loop with assumed flows that already balance at the junctions.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.