FireCADCalc

Economic Diameter of a Pumping Main

Economic diameter of a rising main by Lea's formula and by the pumping-hours form D = 1.3λ^¼√Q, with the resulting velocities.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationRefinery and petrochemicalChemical and fertiliserPulp and paper

Inputs

Examples: 0.15 m³/s average, pumped 16 h/day0.05 m³/s, 8 h/day

Results

When pumping 8 h a day the pumps deliver 24Q/t, so the velocity in the Lea diameter while running is 3.82 m/s.

Q is the average daily flow; when pumping t hours a day the pumps deliver 24Q/t. Both formulas give about 1 m/s; a full life-cycle cost comparison of pipe and energy is the proper basis.

Lea economic diameter223.61mm
Velocity at D_Lea on the average flow Q1.2732m/s
Diameter for the pumping hours382.57mm
Velocity at D_λ (on peak flow 24Q/t)1.3049m/s

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 0.15 m³/s average, pumped 16 h/day. The inputs, in the units selected above:

InputValue
Flow540.00 m³/h
Lea coefficient (0.97–1.22)1.1000 -
Pumping hours per day16.000 h

Applying the formula below gives:

ResultValue
Lea economic diameter426.03 mm
Velocity at D_Lea on the average flow Q1.0523 m/s
Diameter for the pumping hours557.20 mm
Velocity at D_λ (on peak flow 24Q/t)0.92272 m/s

Open this example in the calculator and change any input.

Formula

\(D = k\sqrt Q, \quad D = 1.3\lambda^{1/4}\sqrt{Q_p},\ \lambda = \frac{t}{24}\)

Variables

Symbol Meaning SI unit
\(Q\) Flow m³/s
\(k\) Lea coefficient (0.97–1.22) -
\(t\) Pumping hours per day s
\(D_{Lea}\) Lea economic diameter m
\(v_{Lea}\) Velocity at D_Lea on the average flow Q m/s
\(D_\lambda\) Diameter for the pumping hours m
\(v_\lambda\) Velocity at D_λ (on peak flow 24Q/t) m/s

Method and standards

Economic diameter rules.

Where it is used

  • Raw-water and make-up water mains.
  • Effluent rising mains.

Common mistakes

  • Using peak flow in Lea's formula.
  • Ignoring surge in the final choice.

Assumptions and limits

  • Rule-of-thumb economics.
  • Lea's formula is applied to the average daily flow Q; the velocity shown for it is on Q, and the note gives the higher running velocity on 24Q/t. Which flow Lea's k was fitted to is not stated in the source, so treat D_Lea as indicative.

References

  • Lea's formula D = k√Q; D = 1.3λ^¼√Q for pumping λ = t/24 of the day (CPHEEO Manual on Water Supply and Treatment, ch. 6)

Questions and answers

Why is there an economic diameter?

Larger pipes cost more to buy but less to pump through; the total annual cost has a minimum.

Why does pumping time matter?

Pumping for fewer hours means a higher flow rate while running, so a larger pipe.

What do the defaults represent?

A 0.15 m³/s average flow pumped 16 hours a day.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.