Worked example
Example: Illustrative 30 MPa, s = 5. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Characteristic strength required | 30.000 MPa |
| Assumed standard deviation | 5.0000 MPa |
| Statistical factor (1.65 for 5 % below) | 1.6500 - |
| Mean of test results | 37.500 MPa |
| Standard deviation of test results | 4.2000 MPa |
Applying the formula below gives:
| Result | Value |
|---|---|
| Target mean strength | 38.250 MPa |
| Characteristic strength from tests | 30.570 MPa |
| Margin over requirement | 0.57000 MPa |
| Expected share below f_ck from the tests | 3.7073 % |
Open this example in the calculator and change any input.
Formula
\(f_t = f_{ck} + ks, \quad f_{c,k} = \bar f - ks_m\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(f_{ck}\) | Characteristic strength required | Pa |
| \(s\) | Assumed standard deviation | Pa |
| \(k\) | Statistical factor (1.65 for 5 % below) | - |
| \(\bar f\) | Mean of test results | Pa |
| \(s_m\) | Standard deviation of test results | Pa |
| \(f_t\) | Target mean strength | Pa |
| \(f_{c,k}\) | Characteristic strength from tests | Pa |
| \(f_{c,k} - f_{ck}\) | Margin over requirement | Pa |
| \(p\) | Expected share below f_ck from the tests | - |
Method and standards
Characteristic strength.
Where it is used
- Concrete mix design.
- Site quality control and acceptance.
Common mistakes
- Using too few results for a standard deviation.
- Confusing cube and cylinder strengths.
Assumptions and limits
- Normal distribution of strengths.
References
- Statistical basis of characteristic strength
Questions and answers
Why aim above the required strength?
Concrete strength varies; aiming at the mean plus 1.65 standard deviations keeps about 95 % of results above the characteristic value.
What standard deviation is typical?
About 3.5–6 MPa depending on site control; good ready-mix plants achieve the lower values.
What do the defaults represent?
An illustrative 30 MPa concrete designed with s = 5 MPa, and test results averaging 37.5 MPa with 4.2 MPa standard deviation.