Steam Turbine Heat Rate (kJ/kWh)

Turbine (cycle) heat rate in kJ/kWh and kcal/kWh from main steam flow and conditions, feedwater temperature and generator output, with the cycle efficiency.

Thermal power plantSugar mill and cogenerationChemical and fertiliserPulp and paperIAPWS-IF97 (water and steam)Steam turbineBoiler operation engineer (BOE) examinations

Inputs

Examples: 15 MW condensing, 60 t/h at 66 bar(a) / 485 °C, feed 150 °CBack-pressure 2 MW, 30 t/h at 45 bar(a) / 400 °C, feed 105 °CUtility 210 MW, 640 t/h at 150 bar(a) / 535 °C, feed 240 °C

Results

Turbine heat rate7,223.9kJ/kWh
Turbine cycle efficiency49.834%
Heat added to the steam421.40MW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 15 MW condensing, 60 t/h at 66 bar(a) / 485 °C, feed 150 °C. The inputs, in the units selected above:

InputValue
Main steam flow60,000 kg/h
Inlet steam pressure (absolute)66.000 bar
Inlet steam conditionSuperheated at the temperature below
Inlet steam temperature (superheated only)485.00 °C
Final feedwater temperature (boiler inlet)150.00 °C
Generator output15.000 MW

Applying the formula below gives:

ResultValue
Turbine heat rate10,975 kJ/kWh
Turbine cycle efficiency32.803 %
Heat added to the steam45.728 MW

Open this example in the calculator and change any input.

Formula

\(\dot Q = \dot m_s\,(h_1 - h_{fw}) \qquad HR = \frac{\dot Q}{P_{el}} \qquad \eta_c = \frac{P_{el}}{\dot Q} = \frac{1}{HR}\)

Variables

Symbol Meaning SI unit
\(\dot m_s\) main steam flow kg/s
\(p_1\) main steam pressure, absolute Pa
\(\text{state}\) dry saturated or superheated steam –
\(T_1\) main steam temperature K
\(T_{fw}\) final feedwater temperature K
\(P_{el}\) generator output W
\(HR\) turbine heat rate J/J
\(\eta_c\) turbine cycle efficiency –
\(\dot Q\) heat added to the steam W
\(h_1\) main steam enthalpy J/kg
\(h_{fw}\) feedwater enthalpy J/kg

Method and standards

Turbine heat rate as heat added to the working fluid per unit of generator output, the definition used in ASME PTC 6 for non-reheat units, with enthalpies from FireCAD's IAPWS-IF97. Shown in kJ/kWh; 3600 kJ/kWh is 100 % efficiency.

Where it is used

  • Acceptance and periodic tests of turbo-generators.
  • Comparing turbine offers and checking design heat balances.
  • Converting to plant heat rate and fuel consumption.

Common mistakes

  • Using the boiler outlet feedwater temperature before the last heater.
  • Mixing gross (generator) and net (after auxiliaries) output.
  • Leaving out reheat heat for reheat units.

Assumptions and limits

  • Non-reheat cycle; feedwater enthalpy at main steam pressure (the real feed pressure is higher; small effect); output measured at the generator terminals.
  • For back-pressure (cogeneration) sets all the heat is charged to power, with no credit for the process steam: the heat rate is then very high and not a measure of the turbine's quality.
  • Output above the heat added is rejected.

References

  • IAPWS R7-97(2012) IF97
  • ASME PTC 6 (turbine heat rate definition)

Questions and answers

How is turbine heat rate calculated?

Heat added to the steam per kWh generated. 60 t/h at 66 bar(a) and 485 °C from feedwater at 150 °C takes 45.7 MW of heat; at 15 MW output the heat rate is 10 975 kJ/kWh (2621 kcal/kWh), a cycle efficiency of 32.8 %.

What is the difference from plant heat rate?

Plant heat rate divides the fuel heat by the output, so it includes the boiler efficiency. Turbine heat rate ÷ boiler efficiency ≈ plant heat rate.

My turbine has reheat. Can I use this?

Not directly: add the reheat heat, m_rh (h_hot RH − h_cold RH), to the heat added. This calculator covers non-reheat sets.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.