FireCADCalc

Tube Wall Thinning Rate and Remaining Life

Thinning rate from two wall-thickness surveys and the remaining life until a minimum thickness (entered by the user from the design code).

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolBoiler

Inputs

Examples: 5.0 to 4.6 mm in 2 yearsFast erosion

Results

Linear extrapolation: erosion and corrosion rates change with fuel, velocity and soot blowing. Re-survey before the predicted date.

Thinning rate0.20000mm/a
Remaining life4.0000a

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 5.0 to 4.6 mm in 2 years. The inputs, in the units selected above:

InputValue
Thickness at first survey5.0000 mm
Thickness at second survey4.6000 mm
Time between surveys2.0000 a
Minimum allowed thickness3.8000 mm

Applying the formula below gives:

ResultValue
Thinning rate0.20000 mm/a
Remaining life4.0000 a

Open this example in the calculator and change any input.

Formula

\(\dot t = \frac{t_1 - t_2}{\Delta t}, \quad L = \frac{t_2 - t_{min}}{\dot t}\)

Variables

Symbol Meaning SI unit
\(t_1\) Thickness at first survey m
\(t_2\) Thickness at second survey m
\(\Delta t\) Time between surveys s
\(t_{min}\) Minimum allowed thickness m
\(\dot t\) Thinning rate m/s
\(L\) Remaining life s

Method and standards

Linear extrapolation of the thinning between two surveys at the same points to the minimum thickness. A tube already at or below the minimum is shown with zero remaining life.

Where it is used

  • Shutdown planning.
  • Fuel change reviews.

Common mistakes

  • Mixing UT points.

Assumptions and limits

  • Constant rate.
  • Ultrasonic readings carry an uncertainty (often around ±0.1 mm); when the loss between surveys is small the rate is uncertain, and a note says so.

References

  • Linear extrapolation of two surveys; minimum thickness from the applicable design code
  • entered by the user

Questions and answers

Where does the minimum thickness come from?

From the design code calculation for the tube's pressure and temperature (not reproduced here).

Why measure at the same points?

Thinning varies locally; compare like with like.

Fuel change?

Bagasse with sand or husk with silica erodes much faster: shorten the interval.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.