Worked example
Example: 5.0 to 4.6 mm in 2 years. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Thickness at first survey | 5.0000 mm |
| Thickness at second survey | 4.6000 mm |
| Time between surveys | 2.0000 a |
| Minimum allowed thickness | 3.8000 mm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Thinning rate | 0.20000 mm/a |
| Remaining life | 4.0000 a |
Open this example in the calculator and change any input.
Formula
\(\dot t = \frac{t_1 - t_2}{\Delta t}, \quad L = \frac{t_2 - t_{min}}{\dot t}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(t_1\) | Thickness at first survey | m |
| \(t_2\) | Thickness at second survey | m |
| \(\Delta t\) | Time between surveys | s |
| \(t_{min}\) | Minimum allowed thickness | m |
| \(\dot t\) | Thinning rate | m/s |
| \(L\) | Remaining life | s |
Method and standards
Linear extrapolation of the thinning between two surveys at the same points to the minimum thickness. A tube already at or below the minimum is shown with zero remaining life.
Where it is used
- Shutdown planning.
- Fuel change reviews.
Common mistakes
- Mixing UT points.
Assumptions and limits
- Constant rate.
- Ultrasonic readings carry an uncertainty (often around ±0.1 mm); when the loss between surveys is small the rate is uncertain, and a note says so.
References
- Linear extrapolation of two surveys; minimum thickness from the applicable design code
- entered by the user
Questions and answers
Where does the minimum thickness come from?
From the design code calculation for the tube's pressure and temperature (not reproduced here).
Why measure at the same points?
Thinning varies locally; compare like with like.
Fuel change?
Bagasse with sand or husk with silica erodes much faster: shorten the interval.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.