Worked example
Example: 70 bar, 10 %. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pressure (absolute) | 70.000 bar |
| Steam quality (mass) | 10.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Saturated water density | 739.72 kg/m³ |
| Saturated steam density | 36.524 kg/m³ |
| Void fraction, homogeneous | 69.234 % |
| Mixture density, homogeneous | 252.87 kg/m³ |
| Void fraction, Zivi slip | 45.223 % |
| Mixture density, Zivi | 421.72 kg/m³ |
Open this example in the calculator and change any input.
Formula
\(\alpha = \frac{1}{1 + \frac{1-x}{x}\frac{\rho_v}{\rho_l} S}, \quad \rho = \alpha\rho_v + (1-\alpha)\rho_l, \quad S_Z = (\rho_l/\rho_v)^{1/3}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(p\) | Pressure (absolute) | Pa |
| \(x\) | Steam quality (mass) | - |
| \(\rho_l\) | Saturated water density | kg/m³ |
| \(\rho_v\) | Saturated steam density | kg/m³ |
| \(\alpha_h\) | Void fraction, homogeneous | - |
| \(\rho_h\) | Mixture density, homogeneous | kg/m³ |
| \(\alpha_Z\) | Void fraction, Zivi slip | - |
| \(\rho_Z\) | Mixture density, Zivi | kg/m³ |
Method and standards
Void fraction from the quality and the saturated densities (IAPWS-IF97) with a slip ratio S: S = 1 for the homogeneous model and S = (ρ_l/ρ_v)^1/3 for Zivi; the mixture density is the void-weighted mean. At zero quality the void fraction is zero and the density that of saturated water.
Where it is used
- Natural circulation design.
- Drum and riser studies.
Common mistakes
- Quality by volume entered.
Assumptions and limits
- Saturated two-phase flow.
- Zivi's slip is derived for annular flow; in bubbly and churn flow at low quality (typical of risers) it tends to underpredict the void, so the mixture density and circulation head it gives are on the high side. Use a drift-flux model for those regimes.
References
- Homogeneous model; Zivi (1964) slip S = (ρ_l/ρ_v)^1/3; saturated densities from IAPWS-IF97 (Collier and Thome, Convective Boiling and Condensation)
Questions and answers
Why does a little steam give a large void fraction?
Steam is far less dense than water, so a few per cent by mass fills much of the volume at low pressure.
Which model?
Homogeneous gives the lowest density; slip models give more realistic heads.
Use?
Circulation heads, level measurement and pressure drop.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.