FireCADCalc

Hydrotest: Water to Pressurise and Pressure Drop per Litre

Extra water needed to raise a filled boiler or vessel to test pressure by water compressibility (IF97), and the pressure fall caused by each litre that leaks.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationDistillery and ethanolIAPWS-IF97 (water and steam)Boiler

Inputs

Examples: 60 m3 to 160 barSmall vessel

Results

Rigid shell assumed. The shell also stretches under pressure: for large thin vessels this can add as much water as the compression, or more, and lowers the pressure fall per litre. Air pockets add much more.

Water mass to add2.6027kg
Water volume to add (at starting pressure)2.6104L
Pressure fall for each litre leaked (pressure per L)11.105bar

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 60 m3 to 160 bar. The inputs, in the units selected above:

InputValue
Water volume of the system60.000 m³
Water temperature30.000 °C
Starting pressure (absolute)1.0132 bar
Test pressure (absolute)160.00 bar

Applying the formula below gives:

ResultValue
Water mass to add417.56 kg
Water volume to add (at starting pressure)419.38 L
Pressure fall for each litre leaked (pressure per L)0.37910 bar

Open this example in the calculator and change any input.

Formula

\(\Delta m = V[\rho(p_2, T) - \rho(p_1, T)], \quad \Delta V = \frac{\Delta m}{\rho_1}, \quad \Delta p/L = \frac{p_2 - p_1}{\Delta V / 0.001\ \text{m}^3}\)

Variables

Symbol Meaning SI unit
\(V\) Water volume of the system m³
\(T\) Water temperature K
\(p_1\) Starting pressure (absolute) Pa
\(p_2\) Test pressure (absolute) Pa
\(\Delta m\) Water mass to add kg
\(\Delta V\) Water volume to add (at starting pressure) m³
\(\Delta p/L\) Pressure fall for each litre leaked Pa per L
\(\rho_1, \rho(p, T)\) Water density at the starting pressure; at pressure p and T (IF97) kg/m³

Method and standards

Mass balance at constant temperature: the water added is the system volume times the rise in IAPWS-IF97 density from the starting to the test pressure. The pressure fall per litre leaked is the pressure rise divided by that added volume in litres, a linear (constant compressibility) estimate.

Where it is used

  • Hydrotest planning.
  • Leak-rate judgement during tests.

Common mistakes

  • Ignoring trapped air.

Assumptions and limits

  • Rigid shell; constant temperature. Shell dilation can add a comparable volume for large thin vessels, so the water needed is then higher and the pressure fall per litre lower.

References

  • Mass balance with IAPWS-IF97 densities at both pressures (rigid shell); test pressure itself is a code value entered by the user

Questions and answers

Why so little water?

Water is stiff: at 30 °C the IF97 densities give about 0.045 % volume change per 10 bar.

Why does a small leak drop the pressure fast?

Losing the little compression water releases the whole pressure rise.

Air in the system?

Trapped air absorbs far more water and makes the test slow and unsafe: vent it.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.