Water-Cooled Crystalliser Surface and Water (Hugot)

Cooling surface and water of a water-cooled (Werkspoor type) crystalliser from massecuite flow and massecuite and water temperatures (Hugot 34.15–34.17).

Sugar mill and cogenerationCondenser and cooling tower

Inputs

Examples: Hugot example: 25 m3/h A massecuiteC massecuite

Hugot: 1.15–1.20 (Tromp 1.4).
Hugot: A 40–60, B 35–50, C 25 kcal/(m²·h·°C).

Results

Hugot's example: 25 m³/h of A massecuite cooled 70 → 40 °C by water 25 → 50 °C needs about 495 m² and 20 700 kg/h of water.

Heat removed184.22kW
Cooling surface471.28m²
Cooling water9,317.6kg/h
Water per kg massecuite (without allowance)0.51765

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Hugot example: 25 m3/h A massecuite. The inputs, in the units selected above:

InputValue
Massecuite flow25.000 m³/h
Massecuite density1,500.0 kg/m³
Massecuite specific heat1.6747 kJ/(kg·K)
Allowance factor1.1500 -
Heat-transfer coefficient69.780 W/(m²·K)
Massecuite in70.000 °C
Massecuite out40.000 °C
Water in25.000 °C
Water out50.000 °C

Applying the formula below gives:

ResultValue
Heat removed601.85 kW
Cooling surface496.25 m²
Cooling water20,700 kg/h
Water per kg massecuite (without allowance)0.48000

Open this example in the calculator and change any input.

Formula

\(\dot Q = \alpha V d c (T_0 - T), \quad S = \frac{\dot Q}{k\,\Delta T_{lm}}, \quad \Delta T_{lm} = \frac{(T_0 - t) - (T - t_0)}{\ln\frac{T_0 - t}{T - t_0}}, \quad W = \frac{\dot Q}{c_w(t - t_0)}\)

Variables

Symbol Meaning SI unit
\(V\) Massecuite flow m³/s
\(d\) Massecuite density kg/m³
\(c\) Massecuite specific heat J/(kg·K)
\(\alpha\) Allowance factor -
\(k\) Heat-transfer coefficient W/(m²·K)
\(T_0\) Massecuite in K
\(T\) Massecuite out K
\(t_0\) Water in K
\(t\) Water out K
\(\dot Q\) Heat removed W
\(S\) Cooling surface m²
\(W\) Cooling water kg/s
\(w\) Water per kg massecuite (without allowance) -

Method and standards

Hugot's counter-current heat balance.

Where it is used

  • Designing crystalliser cooling elements.
  • Cooling water budgets.

Common mistakes

  • Taking V in t/h.
  • Water outlet above massecuite inlet.

Assumptions and limits

  • Counter-current flow; constant properties.
  • The water ratio w excludes the allowance while the water flow W includes it.
  • The cooling rate of the massecuite (false grain risk) is not checked.

References

  • Hugot
  • Handbook of Cane Sugar Engineering
  • 3rd ed. (Elsevier, 1986)
  • ch. 34
  • water-cooled crystallisers
  • eqns 34.15–34.17 and example
  • pp. 739–744

Questions and answers

Why the allowance α?

Hugot adds 15–20 % for heat of crystallisation and uneven flow.

Which coefficient?

Much lower for C massecuite, and lower again with scale on the elements.

Counter-current?

Yes: the coldest water meets the coldest massecuite, giving the log-mean difference.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.