Worked example
Example: Illustrative DN50 with 25 mm insulation at -15 C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pipe inside diameter | 50.000 mm |
| Pipe outside diameter | 60.000 mm |
| Insulation thickness | 25.000 mm |
| Insulation conductivity | 0.035000 W/(m·K) |
| Outside heat transfer coefficient | 15.000 W/(m²·K) |
| Initial water temperature | 10.000 °C |
| Air temperature | -15.000 °C |
| Fraction of water frozen | 25.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Thermal resistance per metre | 2.9492 |
| Time to cool to 0 °C | 3.4550 h |
| Time to freeze the fraction | 8.9418 h |
| Total time | 12.397 h |
Open this example in the calculator and change any input.
Formula
\(R' = \frac{\ln(r_2/r_1)}{2\pi\lambda} + \frac{1}{2\pi r_2h_o}, \quad t_c = m'c_pR'\ln\frac{T_0 - T_a}{0 - T_a}, \quad t_f = \frac{fm'L_fR'}{0 - T_a}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D_i\) | Pipe inside diameter | m |
| \(D_o\) | Pipe outside diameter | m |
| \(t_{ins}\) | Insulation thickness | m |
| \(\lambda\) | Insulation conductivity | W/(m·K) |
| \(h_o\) | Outside heat transfer coefficient | W/(m²·K) |
| \(T_0\) | Initial water temperature | K |
| \(T_a\) | Air temperature | K |
| \(f\) | Fraction of water frozen | - |
| \(R'\) | Thermal resistance per metre | - |
| \(t_c\) | Time to cool to 0 °C | s |
| \(t_f\) | Time to freeze the fraction | s |
| \(t\) | Total time | s |
Method and standards
Freeze time.
Where it is used
- Frost protection of outdoor pipes and fire mains.
- Deciding on heat tracing or draining.
Common mistakes
- Assuming insulation prevents freezing.
- Ignoring wind on exposed pipes.
Assumptions and limits
- Still water; uniform water temperature.
References
- Lumped cooling and freezing of water in a pipe
Questions and answers
Does insulation stop a pipe freezing?
No, it only delays it; still water in an insulated pipe will freeze if the cold lasts long enough.
Why do small pipes freeze first?
They hold little water per metre relative to their surface, so they lose their heat and latent store fastest.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Incropera and DeWitt, Fundamentals of Heat and Mass Transfer (Wiley)