Worked example
Example: Illustrative 180 m loop. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Length of the circulation loop (flow pipes) | 180.00 m |
| Pipe heat loss coefficient per metre | 0.25000 W/(m·K) |
| Hot water temperature | 60.000 °C |
| Surrounding air temperature | 20.000 °C |
| Allowed temperature drop round the loop | 5.0000 K |
| Return pipe inner diameter | 20.000 mm |
Applying the formula below gives:
| Result | Value |
|---|---|
| Loop heat loss | 1,800.0 W |
| Recirculation mass flow | 309.60 kg/h |
| Recirculation volume flow | 5.2493 L/min |
| Velocity in the return pipe | 0.27848 m/s |
Open this example in the calculator and change any input.
Formula
\(\dot Q = U'L(T_w - T_a), \quad \dot m = \frac{\dot Q}{c_p\Delta T}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(L\) | Length of the circulation loop (flow pipes) | m |
| \(U'\) | Pipe heat loss coefficient per metre | W/(m·K) |
| \(T_w\) | Hot water temperature | K |
| \(T_a\) | Surrounding air temperature | K |
| \(\Delta T\) | Allowed temperature drop round the loop | K |
| \(d\) | Return pipe inner diameter | m |
| \(\dot Q\) | Loop heat loss | W |
| \(\dot m\) | Recirculation mass flow | kg/s |
| \(\dot V\) | Recirculation volume flow | m³/s |
| \(v\) | Velocity in the return pipe | m/s |
Method and standards
Recirculation flow.
Where it is used
- Sizing hot water circulation pumps.
- Hotels, hospitals and large residential buildings.
Common mistakes
- Including branches that are not circulated.
- Ignoring the heat loss of the return pipe itself (include it in L).
Assumptions and limits
- Steady state; uniform insulation; water near 60 °C.
References
- Heat balance of a recirculation loop
Questions and answers
What temperature drop is allowed?
Usually about 5 K, so a loop leaving at 60 °C returns above 55 °C.
Where does the heat loss per metre come from?
From the insulation calculation or manufacturer's data for the pipe and insulation thickness.
What do the defaults represent?
An illustrative 180 m loop of insulated pipe losing 0.25 W/m·K at 60 °C in 20 °C surroundings, 5 K drop, 20 mm return.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
McQuiston, Parker, Spitler and Taherian, Heating, Ventilating and Air Conditioning, and ASHRAE, Principles of Heating, Ventilating and Air Conditioning, 8th ed. (ASHRAE, 2017)