Heat Pump Water Heater: Energy and Saving over Electric

Daily heat for hot water and the electricity used by a heat pump water heater and an electric heater, with the yearly saving and payback.

Inputs

Examples: Illustrative hotel, 2,000 L/dayHome, 200 L/dayHostel, 5,000 L/day, winter COP

Accepted: 10 to 1,000,000 L
Accepted: 0 to 40 °C
Accepted: 30 to 90 °C
Accepted: 1 to 8
Accepted: 50 to 100 %
Accepted: 0 to 366
Accepted: 0 to 1,000
Accepted: 0 to 100,000,000

Results

Heating water needs m c_p ΔT. An electric heater turns each kWh into slightly less than a kWh of hot water after standing losses; a heat pump moves heat from the air, delivering COP kWh of heat per kWh of electricity (seasonal COP 3–4 in warm climates). The saving is the difference in electricity over the year. Hotels, hostels and hospitals with large, steady demand recover the extra cost fastest.

Heat per day258.12kWh
Heat pump electricity per day92.184kWh
Electric heater electricity per day286.79kWh
Saving per year525,448
Payback (years)1.1419

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative hotel, 2,000 L/day. The inputs, in the units selected above:

InputValue
Hot water per day2,000.0 L
Cold water temperature20.000 °C
Hot water temperature60.000 °C
Heat pump seasonal COP3.5000 -
Electric heater efficiency (including standing loss)90.000 %
Days per year365.00 -
Electricity price per kWh8.0000 -
Extra cost of the heat pump300,000 -

Applying the formula below gives:

ResultValue
Heat per day91.774 kWh
Heat pump electricity per day26.221 kWh
Electric heater electricity per day101.97 kWh
Saving per year221,190
Payback (years)1.3563

Open this example in the calculator and change any input.

Formula

\(Q = \rho V c_p (T_o - T_i), \quad E_{hp} = \frac{Q}{COP}, \quad E_e = \frac{Q}{\eta_e}\)

Variables

Symbol Meaning SI unit
\(V\) Hot water per day m³
\(T_i\) Cold water temperature K
\(T_o\) Hot water temperature K
\(COP\) Heat pump seasonal COP -
\(\eta_e\) Electric heater efficiency (including standing loss) -
\(d\) Days per year -
\(c\) Electricity price per kWh -
\(C_x\) Extra cost of the heat pump -
\(Q_d\) Heat per day J
\(E_{hp}\) Heat pump electricity per day J
\(E_e\) Electric heater electricity per day J
\(\Delta C\) Saving per year -
\(t_{pb}\) Payback (years) -

Method and standards

Heat pump water heater.

Where it is used

  • Hotels, hospitals, hostels and homes.
  • Replacing electric or fuel water heaters.

Common mistakes

  • Using the rated COP at high ambient for the whole year.
  • Ignoring standby losses of the electric heater.

Assumptions and limits

  • Water density at about 50 °C; seasonal COP.

References

  • Heating energy and COP comparison

Questions and answers

How much does a heat pump save on 2,000 L/day of 60 °C water?

About 92 kWh of heat a day: about 26 kWh with the heat pump against 102 kWh electric, near 2.2 lakh a year at 8 per kWh.

Does COP fall in winter?

Yes, colder air lowers COP; use a seasonal value for your climate.

What do the defaults represent?

An illustrative hotel heating 2,000 L/day from 20 °C to 60 °C, heat pump COP 3.5 against a 90 % electric heater, all year at 8 per kWh.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.