Worked example
Example: Illustrative DN150 at 1.5 m/s, 90/50 C, 1 km. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Pipe inside diameter | 150.00 mm |
| Water velocity | 1.5000 m/s |
| Supply temperature | 90.000 °C |
| Return temperature | 50.000 °C |
| Route length (flow and return each) | 1,000.0 m |
| Pipe roughness | 0.050000 mm |
| Pump efficiency | 70.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Water mass flow | 94.306 t/h |
| Heat capacity | 4.3888 MW |
| Pressure drop flow and return | 248.61 kPa |
| Pump power | 9.4142 kW |
| Pump power per heat delivered | 0.21451 % |
Open this example in the calculator and change any input.
Formula
\(\dot Q = \rho vA\,(h_s - h_r), \quad \Delta p = 2f\frac{L}{D}\frac{\rho v^2}{2}, \quad P_p = \frac{\dot V\Delta p}{\eta_p}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(D\) | Pipe inside diameter | m |
| \(v\) | Water velocity | m/s |
| \(T_s\) | Supply temperature | K |
| \(T_r\) | Return temperature | K |
| \(L\) | Route length (flow and return each) | m |
| \(\varepsilon\) | Pipe roughness | m |
| \(\eta_p\) | Pump efficiency | - |
| \(\dot m\) | Water mass flow | kg/s |
| \(\dot Q\) | Heat capacity | W |
| \(\Delta p\) | Pressure drop flow and return | Pa |
| \(P_p\) | Pump power | W |
| \(P_p/\dot Q\) | Pump power per heat delivered | - |
Method and standards
Heat main capacity.
Where it is used
- District heating network design.
- Checking spare capacity for new connections.
Common mistakes
- Designing with too small a ΔT.
- Ignoring fittings and valves in Δp.
Assumptions and limits
- Steady flow; equal flow and return length.
References
- Hydraulic and thermal capacity of a heat main
- Darcy–Weisbach with Colebrook friction
Questions and answers
Why does ΔT matter so much?
Heat carried is ṁc_pΔT: doubling the temperature difference doubles capacity with the same pipe and pumping.
How much pump power do networks use?
Usually about 0.5–2 % of the heat delivered; much more means pipes are undersized.
What do the defaults represent?
An illustrative DN150 main at 1.5 m/s with 90 °C supply and 50 °C return over 1 km, smooth steel, 70 % pump.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.