Worked example
Example: Illustrative 2 MW, 6 K design at 4 K. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Cooling load | 2,000.0 kW |
| Design temperature difference | 6.0000 K |
| Actual temperature difference | 4.0000 K |
| Pump power at design flow | 30.000 kW |
| Pump power exponent on flow (3 ideal, 2–2.5 with fixed head) | 2.5000 - |
| Hours per year at this condition | 3,000.0 h |
| Electricity price per kWh | 0.12000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Design flow | 286.13 m³/h |
| Actual flow | 429.20 m³/h |
| Flow increase | 50.000 % |
| Pump power at actual flow | 82.670 kW |
| Extra pump energy per year | 158.01 MWh |
| Extra cost per year | 18,961 |
Open this example in the calculator and change any input.
Formula
\(\dot V = \frac{\dot Q}{\rho c_p\Delta T}, \quad P_a = P_d\left(\frac{\dot V_a}{\dot V_d}\right)^n\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot Q\) | Cooling load | W |
| \(\Delta T_d\) | Design temperature difference | K |
| \(\Delta T_a\) | Actual temperature difference | K |
| \(P_d\) | Pump power at design flow | W |
| \(n\) | Pump power exponent on flow (3 ideal, 2–2.5 with fixed head) | - |
| \(t\) | Hours per year at this condition | s |
| \(c_e\) | Electricity price per kWh | - |
| \(\dot V_d\) | Design flow | m³/s |
| \(\dot V_a\) | Actual flow | m³/s |
| \(\Delta\dot V\) | Flow increase | - |
| \(P_a\) | Pump power at actual flow | W |
| \(\Delta E\) | Extra pump energy per year | J |
| \(\Delta C\) | Extra cost per year | - |
Method and standards
ΔT penalty.
Where it is used
- Chiller plant audits.
- Justifying two-way valves and coil cleaning.
Common mistakes
- Blaming chillers for a coil-side problem.
- Using the ideal cube law with large fixed head.
Assumptions and limits
- Constant load; water properties at 10 °C.
References
- Sensible heat balance of the chilled-water loop with pump affinity
- ASHRAE Handbook of Fundamentals (ASHRAE)
Questions and answers
What is low ΔT syndrome?
Return water comes back colder than designed, so the plant must pump more water and run more chillers to meet the same load.
How much does it cost?
Dropping from 6 K to 4 K raises flow by 50 % and pump power by roughly 1.8 to 3.4 times, depending on the system curve.
What do the defaults represent?
An illustrative 2 MW plant designed for 6 K running at 4 K, 30 kW pumps at design flow, 3,000 hours a year at 0.12 per kWh.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.