Worked example
Example: Illustrative six 4 MW turbines at 33 kV. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Turbines on the string | 6.0000 - |
| Output per turbine | 4.0000 MW |
| Collector voltage (line-to-line) | 33.000 kV |
| Power factor | 95.000 % |
| Cable resistance per km (one phase) | 0.10000 Ω/km |
| Spacing between turbines (and to the substation) | 600.00 m |
Applying the formula below gives:
| Result | Value |
|---|---|
| Current from one turbine | 73.665 A |
| String losses | 88.887 kW |
| Losses as a share of output | 0.37036 % |
| Current in the last segment | 441.99 A |
Open this example in the calculator and change any input.
Formula
\(P_L = 3I_t^2rs\sum_{k=1}^{n}k^2 = 3I_t^2rs\frac{n(n + 1)(2n + 1)}{6}, \quad I_t = \frac{P_t}{\sqrt3V\,pf}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(n\) | Turbines on the string | - |
| \(P_t\) | Output per turbine | W |
| \(V\) | Collector voltage (line-to-line) | V |
| \(pf\) | Power factor | - |
| \(r\) | Cable resistance per km (one phase) | Ω/m |
| \(s\) | Spacing between turbines (and to the substation) | m |
| \(I_t\) | Current from one turbine | A |
| \(P_L\) | String losses | W |
| \(P_L/(nP_t)\) | Losses as a share of output | - |
| \(I_{max}\) | Current in the last segment | A |
Method and standards
Collector losses.
Where it is used
- Array cable design and string layout.
- Energy yield loss budgets.
Common mistakes
- Using full-output losses as annual losses.
- Forgetting the reactive current from cable charging.
Assumptions and limits
- Uniform cable and spacing; identical turbines at full output.
References
- Copper losses in a radial collector feeder
Questions and answers
Why do losses grow so fast with turbines per string?
The cable near the substation carries all turbines' current and loss goes with current squared, so losses rise roughly with n³.
How large are collector losses?
From a few tenths of a per cent to about 2 % at full output, and less over a year, because the turbines rarely run at full power.
What do the defaults represent?
An illustrative string of six 4 MW turbines, 600 m apart, at 33 kV and 0.95 power factor on cable of 0.1 Ω/km.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Manwell, McGowan and Rogers, Wind Energy Explained, 2nd ed. (Wiley, 2009), ch. 9