Worked example
Example: Illustrative 20 km2, 4.2 MW 150 m, 7D x 4D. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Turbine rating | 4.2000 MW |
| Rotor diameter | 150.00 m |
| Spacing along the prevailing wind (diameters) | 7.0000 - |
| Spacing across the wind (diameters) | 4.0000 - |
| Usable site area | 20.000 km² |
| Net capacity factor (after wake and other losses) | 32.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Number of turbines that fit | 31.000 |
| Land per turbine | 0.63000 km² |
| Installed capacity | 130.20 MW |
| Capacity density (MW per km²) | 6.5100 |
| Annual energy | 364.98 GWh |
| Energy density (average W per m² of land) | 2.0832 W/m² |
Open this example in the calculator and change any input.
Formula
\(A_t = s_aD \times s_cD, \quad N = \left\lfloor\frac{A}{A_t}\right\rfloor, \quad E = NP_t\,CF\,8760\,h\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_t\) | Turbine rating | W |
| \(D\) | Rotor diameter | m |
| \(s_a\) | Spacing along the prevailing wind (diameters) | - |
| \(s_c\) | Spacing across the wind (diameters) | - |
| \(A\) | Usable site area | m² |
| \(CF\) | Net capacity factor (after wake and other losses) | - |
| \(N\) | Number of turbines that fit | - |
| \(A_t\) | Land per turbine | m² |
| \(P\) | Installed capacity | W |
| \(P/A\) | Capacity density (MW per km²) | - |
| \(E\) | Annual energy | J |
| \(E/(A\cdot t)\) | Energy density (average W per m² of land) | W/m² |
Method and standards
Wind farm layout arithmetic.
Where it is used
- Early site screening and land negotiations.
- Comparing land use of energy sources.
Common mistakes
- Using equal spacing in all directions at sites with a strong prevailing wind.
- Ignoring setbacks from houses, roads and power lines.
Assumptions and limits
- Regular grid; flat site; one turbine type.
References
- Array spacing and capacity density
Questions and answers
Why is so much land needed?
Turbines must be several diameters apart to limit wake losses; the land between them stays in farming use, so the footprint actually occupied is only a few per cent.
What capacity density is typical?
Packing at 7D × 4D gives about 5–7 MW/km² for modern turbines; whole farms with setbacks and exclusions average about 2–5 MW/km².
What do the defaults represent?
An illustrative 20 km² site with 4.2 MW, 150 m turbines at 7D × 4D spacing and a 32 % net capacity factor.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Manwell, McGowan and Rogers, Wind Energy Explained, 2nd ed. (Wiley, 2009), ch. 9, Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004)