Worked example
Example: Canal drop 30 m. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Flow through the turbine | 9,000.0 m³/h |
| Net head | 30.000 m |
| Overall efficiency (turbine, generator, transformer) | 82.000 % |
| Plant load factor | 45.000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Electrical output | 603.11 kW |
| Annual energy | 2,377.5 MWh |
Open this example in the calculator and change any input.
Formula
\(P = \rho g Q H \eta, \quad E = P\cdot PLF\cdot 8760 \text{ h}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Flow through the turbine | m³/s |
| \(H\) | Net head | m |
| \(\eta\) | Overall efficiency (turbine, generator, transformer) | - |
| \(PLF\) | Plant load factor | - |
| \(P\) | Electrical output | W |
| \(E\) | Annual energy | J |
| \(\rho\) | Water density, taken as 1 000 | kg/m³ |
| \(g\) | Standard gravity, 9.806 65 | m/s² |
Method and standards
Hydraulic power.
Where it is used
- Canal drops and outfalls.
- Captive small hydro.
Common mistakes
- Gross head.
- Efficiency of the turbine alone.
Assumptions and limits
- Steady flow; water density fixed at 1 000 kg/m³.
- Any size: the page notes when the output exceeds 25 MW, the upper limit of small hydro in India (classes differ by country).
References
- P = ρ g Q H η
Questions and answers
2.5 m³/s at 30 m net, 82 %?
About 603 kW; 2377 MWh a year at 45 % PLF.
Cooling water outfalls?
Large flows at a few metres of head can drive small turbines.
Net or gross head?
Net: subtract pipe losses.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.