Worked example
Example: 0.2 L/s all year. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Leak or waste flow | 0.20000 L/s |
| Hours per year | 8,760.0 h |
| Water cost per m³ (supply and treatment) | 60.000 - |
| Pumping energy per m³ (kWh) | 0.40000 - |
| Electricity price per kWh | 8.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Water lost per year | 6,307.2 m³ |
| Water cost per year | 378,432 |
| Pumping cost per year | 20,183 |
| Total per year | 398,615 |
Open this example in the calculator and change any input.
Formula
\(V = \dot V t, \quad C = V(c_w + e_p c_e)\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\dot V\) | Leak or waste flow | m³/s |
| \(t\) | Hours per year | s |
| \(c_w\) | Water cost per m³ (supply and treatment) | - |
| \(e_p\) | Pumping energy per m³ (kWh) | - |
| \(c_e\) | Electricity price per kWh | - |
| \(V\) | Water lost per year | m³ |
| \(C_w\) | Water cost per year | - |
| \(C_e\) | Pumping cost per year | - |
| \(C\) | Total per year | - |
Method and standards
Volume and cost.
Where it is used
- Water audits.
- Cooling tower and boiler house losses.
Common mistakes
- Ignoring treatment cost.
- Intermittent leaks run all year.
Assumptions and limits
The water price and pumping energy are always per cubic metre, whatever unit system is chosen for the flow and volume; convert prices per 1,000 US gallons (÷ 3.785) before entering them.
Constant flow.
References
- Volume = flow × time; cost = volume × (water price + pumping energy × tariff)
Questions and answers
0.2 L/s running all year?
About 6,307 m³: 398,615 a year.
Bucket test?
Litres collected / seconds gives L/s.
DM or treated water?
Its cost per m³ is far higher; use it.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.