Worked example
Example: 70 % flow. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Reduced flow | 70.000 m³/h |
| Design flow | 100.00 m³/h |
| System head at design flow | 50.000 m |
| Static head of the system | 15.000 m |
| Measured input power when throttled | 17.000 kW |
| Pump efficiency at the VFD point | 72.000 % |
| Motor efficiency | 93.000 % |
| Drive efficiency | 97.000 % |
| Liquid density | 1,000.0 kg/m³ |
| Hours per year at this flow | 6,000.0 h |
| Electricity price per kWh | 8.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| System head at the reduced flow | 32.150 m |
| Input power with the VFD | 9.4387 kW |
| Power saved | 7.5613 kW |
| Energy saved per year | 45.368 MWh |
| Cost saved per year | 362,945 |
Open this example in the calculator and change any input.
Formula
\(H = H_s + (H_d - H_s)\left(\frac{Q}{Q_d}\right)^2, \quad P_v = \frac{\rho g Q H}{\eta_p\eta_m\eta_v}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q\) | Reduced flow | m³/s |
| \(Q_d\) | Design flow | m³/s |
| \(H_d\) | System head at design flow | m |
| \(H_s\) | Static head of the system | m |
| \(P_t\) | Measured input power when throttled | W |
| \(\eta_p\) | Pump efficiency at the VFD point | - |
| \(\eta_m\) | Motor efficiency | - |
| \(\eta_v\) | Drive efficiency | - |
| \(\rho\) | Liquid density | kg/m³ |
| \(t\) | Hours per year at this flow | s |
| \(c\) | Electricity price per kWh | - |
| \(H\) | System head at the reduced flow | m |
| \(P_v\) | Input power with the VFD | W |
| \(\Delta P\) | Power saved | W |
| \(\Delta E\) | Energy saved per year | J |
| \(\Delta C\) | Cost saved per year | - |
Method and standards
System curve and hydraulic power.
Where it is used
- Cooling water, feed and process pumps.
- Energy audits.
Common mistakes
- Cube law with high static head.
- Rated instead of measured throttled power.
Assumptions and limits
- Steady duty at the reduced flow, below the design flow (above it the system curve is extrapolated).
- The pump efficiency at the reduced-speed point is your input, read from the pump curve; it is not estimated by the affinity laws.
References
- System curve H = H_s + (H_d − H_s)(Q/Q_d)²; hydraulic power ρgQH; saving against measured throttled power
Questions and answers
70 % flow, 50 m design head with 15 m static, 17 kW throttled?
The VFD needs about 9.4 kW, saving 7.6 kW: about 45 MWh a year at 6000 h, or about 363,000 at 8 per kWh.
Why not the cube law?
Static head stays; only the friction part falls with the square of flow.
Pump efficiency?
It moves along the curve as speed falls; use the value at the new point.