Pump Saving: Throttling Valve vs Variable Speed Drive

Power and energy saved by running a pump on a variable speed drive instead of throttling, from the system curve (static and design heads) and the throttled power.

Thermal power plantProcess steam and utilities

Inputs

Examples: 70 % flowFriction-only loop at 60 %

Results

Static head limits the saving: the cube law applies only to pure friction systems.

System head at the reduced flow32.150m
Input power with the VFD9.4387kW
Power saved7.5613kW
Energy saved per year45.368MWh
Cost saved per year362,945

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 70 % flow. The inputs, in the units selected above:

InputValue
Reduced flow70.000 m³/h
Design flow100.00 m³/h
System head at design flow50.000 m
Static head of the system15.000 m
Measured input power when throttled17.000 kW
Pump efficiency at the VFD point72.000 %
Motor efficiency93.000 %
Drive efficiency97.000 %
Liquid density1,000.0 kg/m³
Hours per year at this flow6,000.0 h
Electricity price per kWh8.0000 -

Applying the formula below gives:

ResultValue
System head at the reduced flow32.150 m
Input power with the VFD9.4387 kW
Power saved7.5613 kW
Energy saved per year45.368 MWh
Cost saved per year362,945

Open this example in the calculator and change any input.

Formula

\(H = H_s + (H_d - H_s)\left(\frac{Q}{Q_d}\right)^2, \quad P_v = \frac{\rho g Q H}{\eta_p\eta_m\eta_v}\)

Variables

Symbol Meaning SI unit
\(Q\) Reduced flow m³/s
\(Q_d\) Design flow m³/s
\(H_d\) System head at design flow m
\(H_s\) Static head of the system m
\(P_t\) Measured input power when throttled W
\(\eta_p\) Pump efficiency at the VFD point -
\(\eta_m\) Motor efficiency -
\(\eta_v\) Drive efficiency -
\(\rho\) Liquid density kg/m³
\(t\) Hours per year at this flow s
\(c\) Electricity price per kWh -
\(H\) System head at the reduced flow m
\(P_v\) Input power with the VFD W
\(\Delta P\) Power saved W
\(\Delta E\) Energy saved per year J
\(\Delta C\) Cost saved per year -

Method and standards

System curve and hydraulic power.

Where it is used

  • Cooling water, feed and process pumps.
  • Energy audits.

Common mistakes

  • Cube law with high static head.
  • Rated instead of measured throttled power.

Assumptions and limits

  • Steady duty at the reduced flow, below the design flow (above it the system curve is extrapolated).
  • The pump efficiency at the reduced-speed point is your input, read from the pump curve; it is not estimated by the affinity laws.

References

  • System curve H = H_s + (H_d − H_s)(Q/Q_d)²; hydraulic power ρgQH; saving against measured throttled power

Questions and answers

70 % flow, 50 m design head with 15 m static, 17 kW throttled?

The VFD needs about 9.4 kW, saving 7.6 kW: about 45 MWh a year at 6000 h, or about 363,000 at 8 per kWh.

Why not the cube law?

Static head stays; only the friction part falls with the square of flow.

Pump efficiency?

It moves along the curve as speed falls; use the value at the new point.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.