Winding Temperature Rise by the Resistance Method

Average winding temperature and temperature rise from cold and hot winding resistances, for copper or aluminium, as in transformer and motor heat-run tests.

Thermal power plantProcess steam and utilitiesSugar mill and cogeneration

Inputs

Examples: Illustrative copper winding heat runAluminium windingMotor stator copper

Accepted: 1E-6 to 1,000,000 Ω
Accepted: -23.15 to 76.85 °C
Accepted: 1E-6 to 1,000,000 Ω
Accepted: -23.15 to 76.85 °C

Results

T₂ = (R₂/R₁)(T₁ + k) − k (°C), with k = 234.5 for copper and 225 for aluminium, the inferred zero-resistance temperatures. The hot resistance is extrapolated back to the instant of shutdown from readings taken as the winding cools. The result is the average winding temperature; the hot spot is higher.

Average hot winding temperature89.257°C
Winding temperature rise49.257K
Resistance ratio1.2476

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative copper winding heat run. The inputs, in the units selected above:

InputValue
Conductor materialCopper (k = 234.5)
Cold resistance0.45200 Ω
Winding temperature at cold measurement20.000 °C
Hot resistance at shutdown0.57100 Ω
Cooling medium temperature at the end of the test30.000 °C

Applying the formula below gives:

ResultValue
Average hot winding temperature87.003 °C
Winding temperature rise57.003 K
Resistance ratio1.2633

Open this example in the calculator and change any input.

Formula

\(T_2 = \frac{R_2}{R_1}(T_1 + k) - k, \quad \Delta T_w = T_2 - T_a\)

Variables

Symbol Meaning SI unit
\(\text{conductor}\) Conductor material -
\(R_1\) Cold resistance Ω
\(T_1\) Winding temperature at cold measurement K
\(R_2\) Hot resistance at shutdown Ω
\(T_a\) Cooling medium temperature at the end of the test K
\(T_2\) Average hot winding temperature K
\(\Delta T_w\) Winding temperature rise K
\(R_2/R_1\) Resistance ratio -

Method and standards

Resistance method.

Where it is used

  • Transformer and motor heat-run tests.
  • Checking overload temperature in service.

Common mistakes

  • Measuring cold resistance before the winding reaches ambient.
  • Using the copper constant for aluminium.

Assumptions and limits

  • Uniform winding temperature change; linear resistance-temperature relation.

References

  • Resistance method of temperature rise

Questions and answers

Why 234.5 for copper?

Copper's resistance extrapolates to zero at about −234.5 °C, so resistance is proportional to T + 234.5.

Why extrapolate to shutdown?

The winding cools quickly once power is removed; readings over the first minutes are extrapolated back to zero time.

What do the defaults represent?

An illustrative copper winding measuring 0.452 Ω cold at 20 °C and 0.571 Ω hot, with 30 °C cooling air at the end of the run.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Harlow (ed.), Electric Power Transformer Engineering, 3rd ed. (CRC, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.