Worked example
Example: Illustrative 110 % load at 30 C for 24 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Ambient temperature | 30.000 °C |
| Load (per unit of rating) | 1.1000 - |
| Rated top-oil rise | 55.000 K |
| Rated hot-spot rise over top oil | 25.000 K |
| Ratio of load loss to no-load loss at rated load | 6.0000 - |
| Oil exponent | 0.90000 - |
| Winding exponent | 0.80000 - |
| Duration at this condition | 24.000 h |
| Normal insulation life | 180,000 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Top-oil temperature | 93.835 °C |
| Hot-spot temperature | 122.95 °C |
| Ageing acceleration factor | 3.6010 |
| Equivalent ageing time | 86.424 h |
| Loss of life | 0.048014 % |
Open this example in the calculator and change any input.
Formula
\(\theta_H = \theta_a + \Delta\theta_{TO,R}\left(\frac{K^2R + 1}{R + 1}\right)^n + \Delta\theta_{H,R}K^{2m}, \quad F_{AA} = e^{\frac{15000}{383} - \frac{15000}{\theta_H + 273}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\theta_a\) | Ambient temperature | K |
| \(K\) | Load (per unit of rating) | - |
| \(\Delta\theta_{TO,R}\) | Rated top-oil rise | K |
| \(\Delta\theta_{H,R}\) | Rated hot-spot rise over top oil | K |
| \(R\) | Ratio of load loss to no-load loss at rated load | - |
| \(n\) | Oil exponent | - |
| \(m\) | Winding exponent | - |
| \(t\) | Duration at this condition | s |
| \(L_n\) | Normal insulation life | s |
| \(\theta_{TO}\) | Top-oil temperature | K |
| \(\theta_H\) | Hot-spot temperature | K |
| \(F_{AA}\) | Ageing acceleration factor | - |
| \(t_{eq}\) | Equivalent ageing time | s |
| \(LOL\) | Loss of life | - |
Method and standards
Ageing model.
Where it is used
- Overload planning and asset management.
- Ambient derating checks.
Common mistakes
- Treating steady temperatures as reached within an hour.
- Using ageing rates for non-upgraded paper with the 110 °C reference.
Assumptions and limits
- Steady state; thermally upgraded paper.
References
- Thermal model and Arrhenius ageing of transformer insulation
- Transformer loading guide practice (Arrhenius ageing, ultimate temperature rises)
Questions and answers
How fast does insulation age when hot?
Ageing roughly doubles for every 6–7 K above a 110 °C hot spot.
Can I overload a transformer?
For short periods and in cool weather, yes: low ambient and light prior load leave thermal margin, which this steady calculation shows conservatively.
What do the defaults represent?
An illustrative ONAN transformer at 110 % load on a 30 °C day, rated rises 55 K top oil and 25 K hot-spot gradient, held for 24 hours.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.