Transformer Hot-Spot Temperature and Insulation Ageing

Steady top-oil and hot-spot temperature of an oil-filled transformer at a load and ambient, the ageing acceleration factor and loss of life over a period.

Thermal power plantProcess steam and utilities

Inputs

Examples: Illustrative 110 % load at 30 C for 24 hRated load at 20 C130 % overload at 10 C for 4 h

Accepted: -40 to 60 °C
Accepted: 0 to 2
Accepted: 20 to 80 K
Accepted: 5 to 50 K
Accepted: 0.5 to 20
Accepted: 0.5 to 1.2
Accepted: 0.5 to 1.2
Accepted: 1 to 277,780 h
Accepted: 10,000 to 2,777,800 h

Results

Ultimate (steady) temperatures: Δθ_TO = Δθ_TO,R((K²R + 1)/(R + 1))ⁿ, Δθ_H = Δθ_H,R·K^(2m); ageing F_AA = exp(15000/383 − 15000/(θ_H + 273)) relative to 110 °C hot spot for thermally upgraded paper. Short overloads are less severe than this steady value because oil heats with a time constant of hours.

Top-oil temperature93.555°C
Hot-spot temperature131.60°C
Ageing acceleration factor8.0884
Equivalent ageing time32.353h
Loss of life0.017974%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 110 % load at 30 C for 24 h. The inputs, in the units selected above:

InputValue
Ambient temperature30.000 °C
Load (per unit of rating)1.1000 -
Rated top-oil rise55.000 K
Rated hot-spot rise over top oil25.000 K
Ratio of load loss to no-load loss at rated load6.0000 -
Oil exponent0.90000 -
Winding exponent0.80000 -
Duration at this condition24.000 h
Normal insulation life180,000 h

Applying the formula below gives:

ResultValue
Top-oil temperature93.835 °C
Hot-spot temperature122.95 °C
Ageing acceleration factor3.6010
Equivalent ageing time86.424 h
Loss of life0.048014 %

Open this example in the calculator and change any input.

Formula

\(\theta_H = \theta_a + \Delta\theta_{TO,R}\left(\frac{K^2R + 1}{R + 1}\right)^n + \Delta\theta_{H,R}K^{2m}, \quad F_{AA} = e^{\frac{15000}{383} - \frac{15000}{\theta_H + 273}}\)

Variables

Symbol Meaning SI unit
\(\theta_a\) Ambient temperature K
\(K\) Load (per unit of rating) -
\(\Delta\theta_{TO,R}\) Rated top-oil rise K
\(\Delta\theta_{H,R}\) Rated hot-spot rise over top oil K
\(R\) Ratio of load loss to no-load loss at rated load -
\(n\) Oil exponent -
\(m\) Winding exponent -
\(t\) Duration at this condition s
\(L_n\) Normal insulation life s
\(\theta_{TO}\) Top-oil temperature K
\(\theta_H\) Hot-spot temperature K
\(F_{AA}\) Ageing acceleration factor -
\(t_{eq}\) Equivalent ageing time s
\(LOL\) Loss of life -

Method and standards

Ageing model.

Where it is used

  • Overload planning and asset management.
  • Ambient derating checks.

Common mistakes

  • Treating steady temperatures as reached within an hour.
  • Using ageing rates for non-upgraded paper with the 110 °C reference.

Assumptions and limits

  • Steady state; thermally upgraded paper.

References

  • Thermal model and Arrhenius ageing of transformer insulation
  • Transformer loading guide practice (Arrhenius ageing, ultimate temperature rises)

Questions and answers

How fast does insulation age when hot?

Ageing roughly doubles for every 6–7 K above a 110 °C hot spot.

Can I overload a transformer?

For short periods and in cool weather, yes: low ambient and light prior load leave thermal margin, which this steady calculation shows conservatively.

What do the defaults represent?

An illustrative ONAN transformer at 110 % load on a 30 °C day, rated rises 55 K top oil and 25 K hot-spot gradient, held for 24 hours.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.