Transformer Magnetising Inrush Peak (Air-Core Saturation Estimate)

Peak magnetising inrush current of a transformer energised at voltage zero with remanence, from turns, winding height and flux densities, and its multiple.

Thermal power plantProcess steam and utilitiesSugar mill and cogeneration

Inputs

Examples: Illustrative 600-turn winding, 0.8 T remanenceDistribution transformer HV, 1.6 TNo remanence

Accepted: 10 to 100,000
Accepted: 50 to 5,000 mm
Accepted: 0.5 to 2 T
Accepted: -1.5 to 1.5 T
Accepted: 1 to 2.5 T
Accepted: 0.1 to 100,000 A

Results

Switching at voltage zero drives the flux to 2B_n + B_r; the part above saturation must be supplied by the winding as an air-core coil, i_pk ≈ h_w(2B_n + B_r − B_s)/(μ₀N). Source impedance and winding resistance reduce it, and it decays over cycles to seconds. Typical results are 5–15 times rated peak for large units, more for small ones; energising the outer winding gives less.

Peak flux demanded3.9000T
Flux beyond saturation1.9000T
Peak inrush current302.39A
Multiple of rated peak current40.729

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 600-turn winding, 0.8 T remanence. The inputs, in the units selected above:

InputValue
Turns of the energised winding600.00 -
Winding height1,000.0 mm
Rated peak flux density1.7000 T
Remanent flux density0.80000 T
Saturation flux density of the core2.0300 T
Rated rms current of that winding105.00 A

Applying the formula below gives:

ResultValue
Peak flux demanded4.2000 T
Flux beyond saturation2.1700 T
Peak inrush current2,878.1 A
Multiple of rated peak current19.382

Open this example in the calculator and change any input.

Formula

\(B_{pk} = 2B_n + B_r, \quad i_{pk} \approx \frac{h_w(2B_n + B_r - B_s)}{\mu_0N}\)

Variables

Symbol Meaning SI unit
\(N\) Turns of the energised winding -
\(h_w\) Winding height m
\(B_n\) Rated peak flux density T
\(B_r\) Remanent flux density T
\(B_s\) Saturation flux density of the core T
\(I_r\) Rated rms current of that winding A
\(B_{pk}\) Peak flux demanded T
\(\Delta B\) Flux beyond saturation T
\(i_{pk}\) Peak inrush current A
\(i_{pk}/(\sqrt2I_r)\) Multiple of rated peak current -

Method and standards

Inrush estimate.

Where it is used

  • Protection settings and fuse selection.
  • Voltage dip studies when energising transformers.

Common mistakes

  • Ignoring source impedance for small transformers on weak supplies.
  • Assuming zero remanence after a test.

Assumptions and limits

  • Single phase, worst-case switching instant; resistance and source impedance neglected.

References

  • Air-core saturation estimate of inrush

Questions and answers

Why is inrush worst at voltage zero?

Flux must start a full positive half cycle from the remanent value, reaching about twice the normal peak.

How is inrush told apart from a fault by protection?

Inrush is rich in second harmonic; differential relays block on it, typically above 15–20 % of fundamental.

What do the defaults represent?

An illustrative winding of 600 turns, 1 m high, rated at 1.7 T with 0.8 T remanence, core saturating at 2.03 T, rated 105 A.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Bertagnolli, Short-Circuit Duty of Power Transformers (ABB, 1996), Kulkarni and Khaparde, Transformer Engineering: Design, Technology and Diagnostics, 2nd ed. (CRC, 2012)

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.