FireCADCalc

PV String Partial Shading Loss with and without Bypass Diodes

Power of a PV string with some cell groups shaded, with bypass diodes skipping the shaded substrings, against a string limited by the shaded cell's current.

Thermal power plant

Inputs

Examples: Illustrative 20 modules, one shaded substringChimney shade: 4 substrings, 80 % shaded cellTwo substrings, 30 % shaded cell, 10 modules

Accepted: 1 to 100
Accepted: 1 to 6
Accepted: 0 to 600
Accepted: 0 to 100 %
Accepted: 1 to 200 V
Accepted: 0.1 to 30 A
Accepted: 0 to 2 V

Results

Simplified series model: each bypassed substring drops its share of voltage plus a diode drop while current stays at I_mp; without bypass the whole string current falls to the shaded cell's (1 − s)I_mp. Inverter MPP tracking picks the better of the two; real I-V curves have several peaks.

Unshaded string power3.9840kW
Power with bypassed substrings3.7107kW
Loss with bypass diodes6.8594%
Power if the string current follows the shaded cell2.7888kW
Loss without bypass30.000%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 20 modules, one shaded substring. The inputs, in the units selected above:

InputValue
Modules in the string20.000 -
Bypass diodes (substrings) per module3.0000 -
Substrings containing a shaded cell1.0000 -
Shaded fraction of the worst cell50.000 %
Module maximum-power voltage41.500 V
Module maximum-power current9.6000 A
Bypass diode forward voltage0.40000 V

Applying the formula below gives:

ResultValue
Unshaded string power7.9680 kW
Power with bypassed substrings7.8314 kW
Loss with bypass diodes1.7149 %
Power if the string current follows the shaded cell3.9840 kW
Loss without bypass50.000 %

Open this example in the calculator and change any input.

Formula

\(P_{bypass} = I_{mp}\left[NV_{mp} - k\left(\frac{V_{mp}}{n_d} + V_d\right)\right], \quad P_{limited} = (1 - s)NV_{mp}I_{mp}\)

Variables

Symbol Meaning SI unit
\(N\) Modules in the string -
\(n_d\) Bypass diodes (substrings) per module -
\(k\) Substrings containing a shaded cell -
\(s\) Shaded fraction of the worst cell -
\(V_{mp}\) Module maximum-power voltage V
\(I_{mp}\) Module maximum-power current A
\(V_d\) Bypass diode forward voltage V
\(P_0\) Unshaded string power W
\(P_{bypass}\) Power with bypassed substrings W
\(1 - P_b/P_0\) Loss with bypass diodes -
\(P_{limited}\) Power if the string current follows the shaded cell W
\(1 - P_n/P_0\) Loss without bypass -

Method and standards

String shading estimate.

Where it is used

  • Rooftop design near chimneys and vents.
  • Diagnosing low string output.

Common mistakes

  • Assuming shading loss is proportional to shaded area.
  • Ignoring diode heating in long shade.

Assumptions and limits

  • Identical modules; simplified I-V behaviour.

References

  • Series-string shading with bypass diodes

Questions and answers

Why can one shaded cell cut a whole string?

Cells in series carry the same current; without bypass diodes the shaded cell limits the current of every module in the string.

What do bypass diodes cost in energy?

A bypassed substring loses its voltage share (a third of a module with three diodes) plus about 0.4 V, far less than the unbypassed loss.

What do the defaults represent?

An illustrative string of 20 modules (three diodes each, 41.5 V, 9.6 A) with one substring holding a half-shaded cell.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 8

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.