Worked example
Example: Illustrative 400 W module at 800 W/m2, 50 C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated power at STC | 0.40000 kW |
| Open-circuit voltage at STC | 49.500 V |
| Maximum-power voltage at STC | 41.500 V |
| Short-circuit current at STC | 10.200 A |
| Maximum-power current at STC | 9.6400 A |
| Current temperature coefficient (per K) | 5.0000e-04 - |
| Voltage temperature coefficient (per K, negative) | -0.002800 - |
| Power temperature coefficient (per K, negative) | -0.003500 - |
| Cells in series | 72.000 - |
| Diode ideality factor | 1.2000 - |
| Irradiance on the module | 0.80000 kW/m² |
| Cell temperature | 50.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Short-circuit current | 8.2620 A |
| Open-circuit voltage | 45.498 V |
| Maximum-power voltage | 38.058 V |
| Maximum-power current | 7.8084 A |
| Maximum power (power-coefficient method) | 0.29200 kW |
| Maximum power from the voltage and current estimates | 0.29717 kW |
| Ratio to rated power | 73.000 % |
Open this example in the calculator and change any input.
Formula
\(I_{sc} = I_{sc,STC}\frac{G}{1000}\left[1 + \alpha(T_c - 25)\right], \quad V_{oc} = V_{oc,STC}\left[1 + \beta(T_c - 25)\right] + N_sn\frac{kT_c}{q}\ln\frac{G}{1000}, \quad P = P_{STC}\frac{G}{1000}\left[1 + \gamma(T_c - 25)\right]\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(P_{STC}\) | Rated power at STC | W |
| \(V_{oc}\) | Open-circuit voltage at STC | V |
| \(V_{mp}\) | Maximum-power voltage at STC | V |
| \(I_{sc}\) | Short-circuit current at STC | A |
| \(I_{mp}\) | Maximum-power current at STC | A |
| \(\alpha\) | Current temperature coefficient (per K) | - |
| \(\beta\) | Voltage temperature coefficient (per K, negative) | - |
| \(\gamma\) | Power temperature coefficient (per K, negative) | - |
| \(N_s\) | Cells in series | - |
| \(n\) | Diode ideality factor | - |
| \(G\) | Irradiance on the module | W/m² |
| \(T_c\) | Cell temperature | K |
| \(P\) | Maximum power (power-coefficient method) | W |
| \(V_{mp}I_{mp}\) | Maximum power from the voltage and current estimates | W |
| \(P/P_{STC}\) | Ratio to rated power | - |
Method and standards
Module translation equations.
Where it is used
- Inverter and string design checks.
- Comparing measured and expected output.
Common mistakes
- Using ambient instead of cell temperature.
- Applying the power coefficient to voltage.
Assumptions and limits
- Crystalline silicon behaviour; series and shunt resistance effects lumped in the coefficients.
References
- Data-sheet translation of PV module characteristics to operating conditions
Questions and answers
How much does heat cost a PV module?
About 0.35 % per kelvin above 25 °C for crystalline silicon: a module at 60 °C produces about 12 % less than at STC.
Why does voltage fall only slightly in low light?
Voltage depends on the logarithm of irradiance, so halving the light lowers V_oc by only a few per cent while current halves.
What do the defaults represent?
An illustrative 400 W, 72-cell module at 800 W/m² and a cell temperature of 50 °C.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources
Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 8