PV Module Output at Any Irradiance and Cell Temperature

Short-circuit current, open-circuit and maximum-power voltage, current and power of a PV module at a given irradiance and cell temperature from its data sheet.

Thermal power plant

Inputs

Examples: Illustrative 400 W module at 800 W/m2, 50 CCold bright day 1000 W/m2, 5 C (V_oc check)Hot dim 300 W/m2, 65 C, 60-cell 300 W

Accepted: 0.001 to 1 kW
Accepted: 1 to 200 V
Accepted: 1 to 200 V
Accepted: 0.1 to 30 A
Accepted: 0.1 to 30 A
Accepted: 0 to 0.002
Accepted: -0.006 to 0
Accepted: -0.008 to 0
Accepted: 1 to 200
Accepted: 1 to 2
Accepted: 0.01 to 1.5 kW/m²
Accepted: -40 to 90 °C

Results

Currents scale with irradiance and α; voltages change with β and by N_s n kT/q ln(G/1000) with irradiance; power by the data-sheet γ. Low-light efficiency of real modules differs by a few per cent; use the maker's low-irradiance data where given.

Short-circuit current10.098A
Open-circuit voltage52.272V
Maximum-power voltage43.824V
Maximum-power current9.5436A
Maximum power (power-coefficient method)0.42800kW
Maximum power from the voltage and current estimates0.41824kW
Ratio to rated power107.00%

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 400 W module at 800 W/m2, 50 C. The inputs, in the units selected above:

InputValue
Rated power at STC0.40000 kW
Open-circuit voltage at STC49.500 V
Maximum-power voltage at STC41.500 V
Short-circuit current at STC10.200 A
Maximum-power current at STC9.6400 A
Current temperature coefficient (per K)5.0000e-04 -
Voltage temperature coefficient (per K, negative)-0.002800 -
Power temperature coefficient (per K, negative)-0.003500 -
Cells in series72.000 -
Diode ideality factor1.2000 -
Irradiance on the module0.80000 kW/m²
Cell temperature50.000 °C

Applying the formula below gives:

ResultValue
Short-circuit current8.2620 A
Open-circuit voltage45.498 V
Maximum-power voltage38.058 V
Maximum-power current7.8084 A
Maximum power (power-coefficient method)0.29200 kW
Maximum power from the voltage and current estimates0.29717 kW
Ratio to rated power73.000 %

Open this example in the calculator and change any input.

Formula

\(I_{sc} = I_{sc,STC}\frac{G}{1000}\left[1 + \alpha(T_c - 25)\right], \quad V_{oc} = V_{oc,STC}\left[1 + \beta(T_c - 25)\right] + N_sn\frac{kT_c}{q}\ln\frac{G}{1000}, \quad P = P_{STC}\frac{G}{1000}\left[1 + \gamma(T_c - 25)\right]\)

Variables

Symbol Meaning SI unit
\(P_{STC}\) Rated power at STC W
\(V_{oc}\) Open-circuit voltage at STC V
\(V_{mp}\) Maximum-power voltage at STC V
\(I_{sc}\) Short-circuit current at STC A
\(I_{mp}\) Maximum-power current at STC A
\(\alpha\) Current temperature coefficient (per K) -
\(\beta\) Voltage temperature coefficient (per K, negative) -
\(\gamma\) Power temperature coefficient (per K, negative) -
\(N_s\) Cells in series -
\(n\) Diode ideality factor -
\(G\) Irradiance on the module W/m²
\(T_c\) Cell temperature K
\(P\) Maximum power (power-coefficient method) W
\(V_{mp}I_{mp}\) Maximum power from the voltage and current estimates W
\(P/P_{STC}\) Ratio to rated power -

Method and standards

Module translation equations.

Where it is used

  • Inverter and string design checks.
  • Comparing measured and expected output.

Common mistakes

  • Using ambient instead of cell temperature.
  • Applying the power coefficient to voltage.

Assumptions and limits

  • Crystalline silicon behaviour; series and shunt resistance effects lumped in the coefficients.

References

  • Data-sheet translation of PV module characteristics to operating conditions

Questions and answers

How much does heat cost a PV module?

About 0.35 % per kelvin above 25 °C for crystalline silicon: a module at 60 °C produces about 12 % less than at STC.

Why does voltage fall only slightly in low light?

Voltage depends on the logarithm of irradiance, so halving the light lowers V_oc by only a few per cent while current halves.

What do the defaults represent?

An illustrative 400 W, 72-cell module at 800 W/m² and a cell temperature of 50 °C.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 8

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.