PV DC Cable Voltage Drop, Loss and Minimum Size

Voltage drop, power loss and minimum copper or aluminium cross-section of a PV string or array DC cable for a loss limit at the conductor temperature.

Thermal power plant

Inputs

Examples: Illustrative 750 V string, 9.6 A, 60 m of 4 mm2 Cu at 70 CArray home run 400 A, 1000 V, 150 m of 240 mm2 AlLow-voltage 48 V off-grid, 40 A, 10 m of 16 mm2 Cu

Accepted: 0.1 to 5,000 A
Accepted: 1 to 2,000 V
Accepted: 0.1 to 5,000 m
Accepted: 0.1 to 1,000 mm²
Accepted: -40 to 120 °C
Accepted: 0.1 to 10 %

Results

Two-wire DC loop R = ρ(T)·2L/A with ρ₂₀ = 1.724 × 10⁻⁸ Ω·m (copper, IEC annealed) or 2.82 × 10⁻⁸ Ω·m (aluminium) and the temperature coefficient. Voltage drop as a fraction equals the power loss fraction. Check current rating and installation derating separately.

Loop resistance (out and back)0.040932Ω
Voltage drop16.373V
Voltage drop1.6373%
Power loss in the cable6.5492kW
Minimum cross-section for the allowed drop261.97mm²

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative 750 V string, 9.6 A, 60 m of 4 mm2 Cu at 70 C. The inputs, in the units selected above:

InputValue
Operating current (I_mp of the string or array)9.6000 A
Operating voltage (V_mp)750.00 V
One-way cable length60.000 m
Conductor cross-section4.0000 mm²
ConductorCopper
Conductor temperature70.000 °C
Allowed voltage drop1.0000 %

Applying the formula below gives:

ResultValue
Loop resistance (out and back)0.61883 Ω
Voltage drop5.9408 V
Voltage drop0.79210 %
Power loss in the cable0.057031 kW
Minimum cross-section for the allowed drop3.1684 mm²

Open this example in the calculator and change any input.

Formula

\(R = \rho_{20}\left[1 + \alpha(T - 20)\right]\frac{2L}{A}, \quad \frac{\Delta V}{V} = \frac{IR}{V}, \quad A_{min} = \frac{\rho\,2LI}{(\Delta V/V)_{max}V}\)

Variables

Symbol Meaning SI unit
\(I\) Operating current (I_mp of the string or array) A
\(V\) Operating voltage (V_mp) V
\(L\) One-way cable length m
\(A\) Conductor cross-section m²
\(\text{material}\) Conductor -
\(T\) Conductor temperature K
\(\Delta V_{max}\) Allowed voltage drop -
\(R\) Loop resistance (out and back) Ω
\(\Delta V\) Voltage drop V
\(\Delta V/V\) Voltage drop -
\(P_{loss}\) Power loss in the cable W
\(A_{min}\) Minimum cross-section for the allowed drop m²

Method and standards

DC loop resistance.

Where it is used

  • String and array cable selection.
  • Loss budgets for energy yield models.

Common mistakes

  • Using the one-way length only.
  • Ignoring conductor temperature.

Assumptions and limits

  • Direct current; uniform temperature.

References

  • Ohm's law with temperature-corrected conductor resistivity

Questions and answers

What DC loss is usual?

Designers aim for 1–1.5 % at maximum power; long runs at low voltage need larger cables or higher string voltage.

Why use the conductor temperature?

Copper resistance rises about 0.4 % per kelvin; cables in sun on a roof can run at 70 °C or more, 20 % above the 20 °C value.

What do the defaults represent?

An illustrative 750 V string at 9.6 A with 60 m one-way of 4 mm² copper at 70 °C, 1 % allowed drop.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Gilbert Masters, Renewable and Efficient Electric Power Systems (Wiley, 2004), ch. 9

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.