Worked example
Example: Illustrative 750 V string, 9.6 A, 60 m of 4 mm2 Cu at 70 C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Operating current (I_mp of the string or array) | 9.6000 A |
| Operating voltage (V_mp) | 750.00 V |
| One-way cable length | 60.000 m |
| Conductor cross-section | 4.0000 mm² |
| Conductor | Copper |
| Conductor temperature | 70.000 °C |
| Allowed voltage drop | 1.0000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Loop resistance (out and back) | 0.61883 Ω |
| Voltage drop | 5.9408 V |
| Voltage drop | 0.79210 % |
| Power loss in the cable | 0.057031 kW |
| Minimum cross-section for the allowed drop | 3.1684 mm² |
Open this example in the calculator and change any input.
Formula
\(R = \rho_{20}\left[1 + \alpha(T - 20)\right]\frac{2L}{A}, \quad \frac{\Delta V}{V} = \frac{IR}{V}, \quad A_{min} = \frac{\rho\,2LI}{(\Delta V/V)_{max}V}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I\) | Operating current (I_mp of the string or array) | A |
| \(V\) | Operating voltage (V_mp) | V |
| \(L\) | One-way cable length | m |
| \(A\) | Conductor cross-section | m² |
| \(\text{material}\) | Conductor | - |
| \(T\) | Conductor temperature | K |
| \(\Delta V_{max}\) | Allowed voltage drop | - |
| \(R\) | Loop resistance (out and back) | Ω |
| \(\Delta V\) | Voltage drop | V |
| \(\Delta V/V\) | Voltage drop | - |
| \(P_{loss}\) | Power loss in the cable | W |
| \(A_{min}\) | Minimum cross-section for the allowed drop | m² |
Method and standards
DC loop resistance.
Where it is used
- String and array cable selection.
- Loss budgets for energy yield models.
Common mistakes
- Using the one-way length only.
- Ignoring conductor temperature.
Assumptions and limits
- Direct current; uniform temperature.
References
- Ohm's law with temperature-corrected conductor resistivity
Questions and answers
What DC loss is usual?
Designers aim for 1–1.5 % at maximum power; long runs at low voltage need larger cables or higher string voltage.
Why use the conductor temperature?
Copper resistance rises about 0.4 % per kelvin; cables in sun on a roof can run at 70 °C or more, 20 % above the 20 °C value.
What do the defaults represent?
An illustrative 750 V string at 9.6 A with 60 m one-way of 4 mm² copper at 70 °C, 1 % allowed drop.
Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.
Sources