Two-Wattmeter Method: Three-Phase Power and Power Factor

Total power, reactive power, apparent power and power factor of a balanced three-phase load from the two wattmeter readings W1 and W2.

Thermal power plantProcess steam and utilities

Inputs

Examples: 8 kW and 4 kW10 kW and -2 kW (low power factor)Equal readings 5 kW (unity)

Results

P = W₁ + W₂ holds for any three-wire load; Q, S, the power factor and φ assume a balanced load.

Total power W₁ + W₂8.0000kW
Reactive power √3 (W₁ − W₂)20.785kvar
Apparent power22.271kVA
Power factor0.35921
Phase angle68.948°

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 8 kW and 4 kW. The inputs, in the units selected above:

InputValue
Reading of wattmeter 1 (the higher)8.0000 kW
Reading of wattmeter 2 (negative if reversed)4.0000 kW

Applying the formula below gives:

ResultValue
Total power W₁ + W₂12.000 kW
Reactive power √3 (W₁ − W₂)6.9282 kvar
Apparent power13.856 kVA
Power factor0.86603
Phase angle30.000 °

Open this example in the calculator and change any input.

Formula

\(P = W_1 + W_2, \quad \tan\varphi = \frac{\sqrt 3\,(W_1 - W_2)}{W_1 + W_2}\)

Variables

Symbol Meaning SI unit
\(W_1\) Reading of wattmeter 1 (the higher) W
\(W_2\) Reading of wattmeter 2 (negative if reversed) W
\(P\) Total power W₁ + W₂ W
\(Q\) Reactive power √3 (W₁ − W₂) var
\(S\) Apparent power VA
\(\cos\varphi\) Power factor -
\(\varphi\) Phase angle rad

Method and standards

Two-wattmeter relations for a balanced three-wire load.

Where it is used

  • Laboratory and site power measurement.
  • Electrical examinations.

Common mistakes

  • Adding a reversed reading as positive.
  • Using it for unbalanced power factor.

Assumptions and limits

  • Total power is valid for unbalanced three-wire loads too (Blondel); the reactive power and power factor are valid for balanced loads only.

  • The sign of Q depends on which meter is W₁ and on the phase sequence; the page warns when W₁ is the lower reading.

  • Balanced load and sinusoidal supply for the power factor.

References

  • Blondel's theorem; two-wattmeter method for balanced loads

Questions and answers

What power factor do readings of 8 kW and 4 kW give?

P = 12 kW, tan φ = √3 × 4/12, power factor 0.866.

When does one wattmeter read zero?

At power factor 0.5 (φ = 60°).

And negative?

Below 0.5 power factor; enter that reading as negative.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.