Worked example
Example: 4 discs, k 0.1, 66 kV line. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Number of discs | 4.0000 - |
| Shunt-to-self capacitance ratio C₁/C | 0.10000 - |
| Phase voltage across the string | 38.105 kV |
Applying the formula below gives:
| Result | Value |
|---|---|
| Voltage across the top disc (furthest from the line) | 7.5292 kV |
| Voltage across the disc nearest the line | 12.431 kV |
| String efficiency | 76.635 % |
Open this example in the calculator and change any input.
Formula
\(I_{j} = I_{j-1} + k\sum_{i<j}V_i\ \text{(per unit)}, \quad \eta = \frac{V}{nV_n}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(n\) | Number of discs | - |
| \(k\) | Shunt-to-self capacitance ratio C₁/C | - |
| \(V\) | Phase voltage across the string | V |
| \(V_1\) | Voltage across the top disc (furthest from the line) | V |
| \(V_n\) | Voltage across the disc nearest the line | V |
| \(\eta\) | String efficiency | - |
Method and standards
Capacitance ladder.
Where it is used
- Insulator string checks.
- Teaching.
Common mistakes
- Using line voltage for the string.
- Forgetting line-side capacitance when guard rings are fitted.
Assumptions and limits
- Uniform discs; capacitance to earth only.
References
- Suspension insulator string theory (self and shunt capacitances)
- as in Kothari–Nagrath and V. K. Mehta
Questions and answers
Why is the voltage uneven?
Leakage through pin-to-earth capacitance means discs nearer the line carry the charging current of all discs above them.
How is it improved?
Longer cross-arms (smaller k), guard rings or grading, and capacitance grading of discs.
What do the defaults represent?
Four discs with k = 0.1 on a 66 kV line.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.