kW to Amps Calculator (DC, Single Phase, Three Phase)

Current drawn by a load from its power in kW, the voltage, power factor and efficiency, for DC, single-phase and three-phase supplies, with kVA and kvar.

Thermal power plantProcess steam and utilities

Inputs

Examples: 75 kW at 415 V, 0.85, three phase2.2 kW motor at 230 V, 0.8, 85 % efficient, single phase5 kW at 48 V DC, 95 % efficient

Results

Current109.65A
Input power5.2632kW
Apparent power5.2632kVA
Reactive power0kvar

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 75 kW at 415 V, 0.85, three phase. The inputs, in the units selected above:

InputValue
Power (output, or input if efficiency is 100 %)75.000 kW
Voltage (line to line for three phase)415.00 V
Power factor (AC)0.85000 -
Efficiency100.00 %
SupplyThree phase AC

Applying the formula below gives:

ResultValue
Current122.75 A
Input power75.000 kW
Apparent power88.235 kVA
Reactive power46.481 kvar

Open this example in the calculator and change any input.

Formula

\(I = \frac{P}{\sqrt 3\, V \cos\varphi\, \eta}\ (3\phi), \quad I = \frac{P}{V \cos\varphi\, \eta}\ (1\phi), \quad I = \frac{P}{V \eta}\ (\text{DC})\)

Variables

Symbol Meaning SI unit
\(P\) Power (output, or input if efficiency is 100 %) W
\(V\) Voltage (line to line for three phase) V
\(\cos\varphi\) Power factor (AC) -
\(\eta\) Efficiency -
\(\text{supply}\) Supply -
\(I\) Current A
\(P_{in}\) Input power W
\(S\) Apparent power VA
\(Q\) Reactive power var

Method and standards

Definition of active power.

Where it is used

  • Feeder and breaker sizing.
  • Checking a nameplate current.

Common mistakes

  • Leaving out power factor.
  • Using 230 V with the three-phase formula.

Assumptions and limits

  • Balanced load, sinusoidal supply.

References

  • AC power relations P = √3 V I cos φ (3φ)
  • P = V I cos φ (1φ)
  • P = V I (DC)

Questions and answers

How many amps does 75 kW take at 415 V, 0.85 power factor?

122.8 A.

Why include efficiency?

A motor's kW is shaft output; the supply delivers output ÷ efficiency.

And for DC?

I = P / V; there is no power factor.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.