kW, kVA, kvar and Power Factor (Power Triangle)

Solves the power triangle: apparent power, power factor and phase angle from kW and kvar, or kvar and kVA from kW and power factor.

Thermal power plantProcess steam and utilitiesElectric motor

Inputs

Examples: 800 kW and 600 kvar500 kW at pf 0.75Leading: 200 kW, -50 kvar

kW and kvar

kW and power factor

Results

Apparent power666.67kVA
Power factor75.000%
Reactive power440.96kvar
Phase angle41.410°
kvar per kW0.88192

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 800 kW and 600 kvar. The inputs, in the units selected above:

InputValue
Known valueskW and kvar
Active power800.00 kW
Reactive power600.00 kvar
Power factor80.000 %

Applying the formula below gives:

ResultValue
Apparent power1,000.0 kVA
Power factor80.000 %
Reactive power600.00 kvar
Phase angle36.870 °
kvar per kW0.75000

Open this example in the calculator and change any input.

Formula

\(S = \sqrt{P^2 + Q^2} \qquad \cos\varphi = \frac{P}{S} \qquad \varphi = \operatorname{atan2}(Q, P) \qquad Q = P\tan(\arccos\cos\varphi)\)

Variables

Symbol Meaning SI unit
\(\text{given}\) which pair is known –
\(P\) active power W
\(Q\) reactive power var
\(\cos\varphi\) power factor –
\(S\) apparent power VA
\(\varphi\) phase angle rad
\(\tan\varphi\) kvar per kW –

Method and standards

Right-angled power triangle of balanced sinusoidal circuits.

Where it is used

  • Tariff power-factor checks.
  • Capacitor bank sizing input.
  • Generator and transformer rating checks.

Common mistakes

  • Adding kVA of loads at different power factors arithmetically.
  • Dropping the sign of leading kvar.

Assumptions and limits

  • Sinusoidal; distortion power from harmonics is not included.
  • With "kW and power factor" the load is taken as lagging (inductive); for a leading (capacitive) load enter kW and a negative kvar.

References

  • IEC 60050-131 (power definitions)

Questions and answers

What are kVA and power factor for 800 kW and 600 kvar?

1000 kVA and power factor 0.80 (phase angle 36.9°).

What does negative kvar mean?

The load is capacitive: power factor leading, as with over-corrected capacitor banks.

How do I find kvar from kW and pf?

kvar = kW × tan(acos pf); at pf 0.75, 500 kW needs 441 kvar.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.