Ferranti Effect: Receiving-End Voltage Rise on an Open Line

Receiving-end voltage rise on a lightly loaded or open line or cable from length, inductance and capacitance per km, with charging current and Mvar.

Thermal power plantProcess steam and utilitiesSugar mill and cogenerationChemical and fertiliserPulp and paperFood, dairy and textile

Inputs

Examples: 220 kV, 300 km overhead33 kV cable 20 km

Results

Lossless distributed line: V_R = V_S/cos(βℓ). Cables have much higher capacitance than overhead lines, so long cables show the effect at shorter lengths.

Receiving-end voltage at no load33.065kV
Voltage rise0.19772%
Charging current at the sending end29.967A
Charging reactive power1.7129Mvar

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 220 kV, 300 km overhead. The inputs, in the units selected above:

InputValue
Sending-end line voltage220.00 kV
Line length300.00 km
Inductance per length1.0000 mH/km
Capacitance per length11.500 nF/km
Frequency50.000 Hz

Applying the formula below gives:

ResultValue
Receiving-end voltage at no load231.74 kV
Voltage rise5.3343 %
Charging current at the sending end142.55 A
Charging reactive power54.321 Mvar

Open this example in the calculator and change any input.

Formula

\(V_R = \frac{V_S}{\cos\beta\ell}, \quad \beta = \omega\sqrt{L'C'}, \quad I_c = \frac{V_S}{\sqrt3Z_c}\tan\beta\ell, \quad Z_c = \sqrt{\frac{L'}{C'}}\)

Variables

Symbol Meaning SI unit
\(V_S\) Sending-end line voltage V
\(\ell\) Line length m
\(L'\) Inductance per km (mH/km) -
\(C'\) Capacitance per km (nF/km) -
\(f\) Frequency 1/s
\(V_R\) Receiving-end voltage at no load V
\(\Delta V/V_S\) Voltage rise -
\(I_c\) Charging current at the sending end A
\(Q_c\) Charging reactive power var

Method and standards

Lossless distributed line.

Where it is used

  • Energising long lines and cables.
  • Shunt reactor sizing.

Common mistakes

  • Using per-km values without length.
  • Applying lossless formulas to very lossy cables.

Assumptions and limits

  • Lossless; open receiving end.
  • L′ in mH/km and C′ in nF/km in every unit system.

References

  • Stevenson and Grainger
  • Power System Analysis (McGraw-Hill, 1994); Kothari and Nagrath
  • Modern Power System Analysis
  • 4th ed. (2011) (lossless line, V_R = V_S/cos βℓ)

Questions and answers

Why does voltage rise at an open end?

Charging current flowing through the line inductance produces a drop that adds to the voltage along the line.

How is it controlled?

Shunt reactors at line ends, or by not energising long lines at no load.

What do the defaults represent?

A 220 kV, 300 km overhead line with typical 1 mH/km and 11.5 nF/km.

Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.