Worked example
Example: 220 kV, 300 km overhead. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Sending-end line voltage | 220.00 kV |
| Line length | 300.00 km |
| Inductance per length | 1.0000 mH/km |
| Capacitance per length | 11.500 nF/km |
| Frequency | 50.000 Hz |
Applying the formula below gives:
| Result | Value |
|---|---|
| Receiving-end voltage at no load | 231.74 kV |
| Voltage rise | 5.3343 % |
| Charging current at the sending end | 142.55 A |
| Charging reactive power | 54.321 Mvar |
Open this example in the calculator and change any input.
Formula
\(V_R = \frac{V_S}{\cos\beta\ell}, \quad \beta = \omega\sqrt{L'C'}, \quad I_c = \frac{V_S}{\sqrt3Z_c}\tan\beta\ell, \quad Z_c = \sqrt{\frac{L'}{C'}}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V_S\) | Sending-end line voltage | V |
| \(\ell\) | Line length | m |
| \(L'\) | Inductance per km (mH/km) | - |
| \(C'\) | Capacitance per km (nF/km) | - |
| \(f\) | Frequency | 1/s |
| \(V_R\) | Receiving-end voltage at no load | V |
| \(\Delta V/V_S\) | Voltage rise | - |
| \(I_c\) | Charging current at the sending end | A |
| \(Q_c\) | Charging reactive power | var |
Method and standards
Lossless distributed line.
Where it is used
- Energising long lines and cables.
- Shunt reactor sizing.
Common mistakes
- Using per-km values without length.
- Applying lossless formulas to very lossy cables.
Assumptions and limits
- Lossless; open receiving end.
- L′ in mH/km and C′ in nF/km in every unit system.
References
- Stevenson and Grainger
- Power System Analysis (McGraw-Hill, 1994); Kothari and Nagrath
- Modern Power System Analysis
- 4th ed. (2011) (lossless line, V_R = V_S/cos βℓ)
Questions and answers
Why does voltage rise at an open end?
Charging current flowing through the line inductance produces a drop that adds to the voltage along the line.
How is it controlled?
Shunt reactors at line ends, or by not energising long lines at no load.
What do the defaults represent?
A 220 kV, 300 km overhead line with typical 1 mH/km and 11.5 nF/km.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.