Worked example
Example: 25 kvar 440 V on 415 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Rated kvar | 25.000 kvar |
| Rated voltage | 440.00 V |
| Rated frequency | 50.000 Hz |
| Actual system voltage | 415.00 V |
| Actual frequency | 50.000 Hz |
Applying the formula below gives:
| Result | Value |
|---|---|
| Actual kvar output | 22.240 kvar |
| Output as a share of the rating | 88.959 % |
| Line current (three phase) | 30.940 A |
| Rated line current (three phase) | 32.804 A |
Open this example in the calculator and change any input.
Formula
\(Q = Q_r \left(\frac{V}{V_r}\right)^2 \frac{f}{f_r}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(Q_r\) | Rated kvar | var |
| \(V_r\) | Rated voltage | V |
| \(f_r\) | Rated frequency | 1/s |
| \(V\) | Actual system voltage | V |
| \(f\) | Actual frequency | 1/s |
| \(Q\) | Actual kvar output | var |
| \(Q/Q_r\) | Output as a share of the rating | - |
| \(I\) | Line current (three phase) | A |
| \(I_r\) | Rated line current (three phase) | A |
Method and standards
Fixed capacitance at another voltage and frequency.
Where it is used
- Selecting capacitor banks.
- Checking measured capacitor current.
Common mistakes
- Assuming rated kvar at system voltage.
- Ignoring detuning reactors, which raise capacitor voltage.
Assumptions and limits
- No series reactor.
- A system voltage above 1.1 times the rating is flagged (IEC 60831-1 admits 1.10 U_N only for limited periods).
References
- Q = ω C V²: output ∝ V² f
Questions and answers
What does a 25 kvar, 440 V capacitor give on 415 V?
22.2 kvar: 89 % of its rating.
Why buy 440 V capacitors for a 415 V system?
For margin against overvoltage and harmonics; allow for the lower output.
And on 60 Hz?
A 50 Hz capacitor gives 20 % more kvar and current.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.