FireCADCalc

Capacitor kvar Output at a Different Voltage and Frequency

Actual kvar and current of a power capacitor used at a voltage and frequency other than its rating, since output varies with voltage squared and frequency.

Thermal power plantProcess steam and utilities

Inputs

Examples: 25 kvar 440 V on 415 V50 kvar 525 V on 400 V10 kvar 480 V 60 Hz on 415 V 50 Hz

Results

Actual kvar output6.2292kvar
Output as a share of the rating62.292%
Line current (three phase)8.6661A
Rated line current (three phase)12.028A

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 25 kvar 440 V on 415 V. The inputs, in the units selected above:

InputValue
Rated kvar25.000 kvar
Rated voltage440.00 V
Rated frequency50.000 Hz
Actual system voltage415.00 V
Actual frequency50.000 Hz

Applying the formula below gives:

ResultValue
Actual kvar output22.240 kvar
Output as a share of the rating88.959 %
Line current (three phase)30.940 A
Rated line current (three phase)32.804 A

Open this example in the calculator and change any input.

Formula

\(Q = Q_r \left(\frac{V}{V_r}\right)^2 \frac{f}{f_r}\)

Variables

Symbol Meaning SI unit
\(Q_r\) Rated kvar var
\(V_r\) Rated voltage V
\(f_r\) Rated frequency 1/s
\(V\) Actual system voltage V
\(f\) Actual frequency 1/s
\(Q\) Actual kvar output var
\(Q/Q_r\) Output as a share of the rating -
\(I\) Line current (three phase) A
\(I_r\) Rated line current (three phase) A

Method and standards

Fixed capacitance at another voltage and frequency.

Where it is used

  • Selecting capacitor banks.
  • Checking measured capacitor current.

Common mistakes

  • Assuming rated kvar at system voltage.
  • Ignoring detuning reactors, which raise capacitor voltage.

Assumptions and limits

  • No series reactor.
  • A system voltage above 1.1 times the rating is flagged (IEC 60831-1 admits 1.10 U_N only for limited periods).

References

  • Q = ω C V²: output ∝ V² f

Questions and answers

What does a 25 kvar, 440 V capacitor give on 415 V?

22.2 kvar: 89 % of its rating.

Why buy 440 V capacitors for a 415 V system?

For margin against overvoltage and harmonics; allow for the lower output.

And on 60 Hz?

A 50 Hz capacitor gives 20 % more kvar and current.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.