Capacitor kvar for an Induction Motor

Capacitor rating to connect at an induction motor's terminals from its no-load current, kept below the magnetising kvar to avoid self-excitation.

Thermal power plantProcess steam and utilitiesElectric motor

Inputs

Examples: 415 V motor, no-load current 52 A6.6 kV motor, 18 A460 V 60 Hz, 30 A, 0.85

Measured with the motor running uncoupled, or from the maker's data; roughly 25–40 % of full-load current for 4-pole motors.
Practice is 0.9 so the capacitor never supplies more than the magnetising kvar at no load.

Results

Take the nearest standard rating below the value. Do not fit motor-terminal capacitors to motors that can be driven by the load (cranes, hoists) or that use star-delta or reversing starters.

Capacitor rating (three-phase)185.19kvar
No-load magnetising kvar205.77kvar
Capacitor line current16.200A
Capacitance per phase, delta connected4.5109µF

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 415 V motor, no-load current 52 A. The inputs, in the units selected above:

InputValue
Line voltage415.00 V
No-load current of the motor52.000 A
Share of the no-load magnetising kvar to supply90.000 %
Supply frequency50.000 Hz

Applying the formula below gives:

ResultValue
Capacitor rating (three-phase)33.640 kvar
No-load magnetising kvar37.378 kvar
Capacitor line current46.800 A
Capacitance per phase, delta connected207.25 µF

Open this example in the calculator and change any input.

Formula

\(Q_0 = \sqrt 3\,V\,I_0 \qquad Q_c = k\,Q_0 \qquad I_c = \frac{Q_c}{\sqrt 3\,V} \qquad C_\Delta = \frac{Q_c}{3\,\omega\,V^2},\ \omega = 2\pi f\)

Variables

Symbol Meaning SI unit
\(V\) line voltage V
\(I_0\) no-load current A
\(k\) share of magnetising kvar –
\(f\) frequency Hz
\(Q_c\) capacitor rating var
\(Q_0\) no-load magnetising kvar var
\(I_c\) capacitor line current A
\(C_\Delta\) Capacitance per phase, delta connected F
\(\omega\) angular frequency rad/s

Method and standards

The no-load current of an induction motor is almost all magnetising current; sizing the capacitor at about 90 % of it corrects most of the motor's reactive power without risk of self-excitation.

Where it is used

  • Large LT motors on long feeders.
  • Pumps and fans running continuously.
  • Reducing cable and transformer current.

Common mistakes

  • Sizing from full-load current.
  • Fitting capacitors to VFD-fed motors.
  • Leaving capacitors on star-delta starters.

Assumptions and limits

  • Direct-on-line motors only; not with variable-frequency drives.
  • The 0.9 share is common practice, not a figure from a standard: enter your own share. The no-load current is taken as wholly magnetising; its small active part is neglected, which slightly oversizes Q₀.

References

  • Motor-terminal capacitor practice (no-load magnetising kvar)

Questions and answers

What capacitor suits a 415 V motor with 52 A no-load current?

33.6 kvar (90 % of the 37.4 kvar magnetising load), drawing 46.8 A; choose the next standard size below.

Why stay below the no-load kvar?

After switch-off a spinning motor with too much capacitance can self-excite and produce dangerous voltages.

Which motors must not get terminal capacitors?

Motors driven by their load (cranes, hoists), reversing or star-delta starters, and motors with frequent jogging.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.