Worked example
Example: 415 V motor, no-load current 52 A. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Line voltage | 415.00 V |
| No-load current of the motor | 52.000 A |
| Share of the no-load magnetising kvar to supply | 90.000 % |
| Supply frequency | 50.000 Hz |
Applying the formula below gives:
| Result | Value |
|---|---|
| Capacitor rating (three-phase) | 33.640 kvar |
| No-load magnetising kvar | 37.378 kvar |
| Capacitor line current | 46.800 A |
| Capacitance per phase, delta connected | 207.25 µF |
Open this example in the calculator and change any input.
Formula
\(Q_0 = \sqrt 3\,V\,I_0 \qquad Q_c = k\,Q_0 \qquad I_c = \frac{Q_c}{\sqrt 3\,V} \qquad C_\Delta = \frac{Q_c}{3\,\omega\,V^2},\ \omega = 2\pi f\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(V\) | line voltage | V |
| \(I_0\) | no-load current | A |
| \(k\) | share of magnetising kvar | – |
| \(f\) | frequency | Hz |
| \(Q_c\) | capacitor rating | var |
| \(Q_0\) | no-load magnetising kvar | var |
| \(I_c\) | capacitor line current | A |
| \(C_\Delta\) | Capacitance per phase, delta connected | F |
| \(\omega\) | angular frequency | rad/s |
Method and standards
The no-load current of an induction motor is almost all magnetising current; sizing the capacitor at about 90 % of it corrects most of the motor's reactive power without risk of self-excitation.
Where it is used
- Large LT motors on long feeders.
- Pumps and fans running continuously.
- Reducing cable and transformer current.
Common mistakes
- Sizing from full-load current.
- Fitting capacitors to VFD-fed motors.
- Leaving capacitors on star-delta starters.
Assumptions and limits
- Direct-on-line motors only; not with variable-frequency drives.
- The 0.9 share is common practice, not a figure from a standard: enter your own share. The no-load current is taken as wholly magnetising; its small active part is neglected, which slightly oversizes Q₀.
References
- Motor-terminal capacitor practice (no-load magnetising kvar)
Questions and answers
What capacitor suits a 415 V motor with 52 A no-load current?
33.6 kvar (90 % of the 37.4 kvar magnetising load), drawing 46.8 A; choose the next standard size below.
Why stay below the no-load kvar?
After switch-off a spinning motor with too much capacitance can self-excite and produce dangerous voltages.
Which motors must not get terminal capacitors?
Motors driven by their load (cranes, hoists), reversing or star-delta starters, and motors with frequent jogging.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.