Single-Phase Motor Full-Load Current and Power

Full-load current, input power, apparent and reactive power of a single-phase motor from rated output, voltage, efficiency and power factor.

Process steam and utilitiesFood, dairy and textileIEC 60034 (rotating machines)Electric motorElectrician and wireman licence examinations

Inputs

Examples: 2.2 kW, 230 V, 82 %, cos 0.900.75 kW, 230 V, 72 %, cos 0.801 hp, 115 V, 70 %, cos 0.78

Results

Full-load current11.876A
Electrical input power1.0653kW
Apparent power1.3658kVA
Reactive power0.85466kvar
Motor losses (heat)0.31959kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2.2 kW, 230 V, 82 %, cos 0.90. The inputs, in the units selected above:

InputValue
Supply voltage230.00 V
Rated shaft output2.2000 kW
Efficiency at full load82.000 %
Power factor at full load0.90000 -

Applying the formula below gives:

ResultValue
Full-load current12.961 A
Electrical input power2.6829 kW
Apparent power2.9810 kVA
Reactive power1.2994 kvar
Motor losses (heat)0.48293 kW

Open this example in the calculator and change any input.

Formula

\(P_{in} = \frac{P_{out}}{\eta} \qquad S = \frac{P_{in}}{\cos\varphi} \qquad I = \frac{S}{U} = \frac{P_{out}}{U\,\eta\,\cos\varphi} \qquad Q = \sqrt{S^2 - P_{in}^2} \qquad P_{loss} = P_{in} - P_{out}\)

Variables

Symbol Meaning SI unit
\(U\) supply voltage V
\(P_{out}\) rated mechanical output at the shaft W
\(\eta\) efficiency at full load –
\(\cos\varphi\) power factor at full load –
\(I\) full-load current A
\(P_{in}\) active electrical input W
\(S\) apparent power VA
\(Q\) reactive power var
\(P_{loss}\) losses dissipated as heat W

Method and standards

Single-phase power relations, with efficiency and power factor as defined in IEC 60034-1. The output may be entered in kW or horsepower (1 hp = 745.70 W).

Where it is used

  • Sizing cables, fuses and starters for single-phase motors.
  • Checking a motor's current against its nameplate.
  • Small pumps, fans and dosing equipment.

Common mistakes

  • Leaving out efficiency and power factor.
  • Using output power as input power.
  • Ignoring starting current for protection.

Assumptions and limits

  • Rated voltage and frequency; full-load efficiency and power factor from the nameplate or data sheet.
  • Both efficiency and power factor fall at part load.

References

  • IEC 60034-1 (rating and performance definitions)

Questions and answers

What current does a 2.2 kW single-phase motor draw?

At 230 V with 82 % efficiency and power factor 0.90, I = 2 200/(230 × 0.82 × 0.90) = 13.0 A.

Why is a single-phase motor current so much higher than a three-phase one?

All the power flows through one pair of conductors, and small single-phase motors have lower efficiency and power factor. A 2.2 kW three-phase motor at 415 V with 85 % efficiency and 0.80 power factor takes about 4.5 A (three-phase motor calculator).

Is this the starting current?

No. Starting current is several times the full-load current; capacitor-start motors typically draw 4 to 6 times it.

Method and article reviewed by FireCAD engineering on 10 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.