FireCADCalc

Motor Energy and Cost from Running Hours

Electrical energy and cost of pump, fan and other motors from their rating, load, efficiency, number running and running hours.

Thermal power plantProcess steam and utilitiesPumpFan and blowerElectric motor

Inputs

Examples: 2 feed pumps of 90 kW at 80 % load, 94 % motor, 24 hID fan 250 kW at 70 %, 95.5 %, 8000 h3 cooling water pumps 37 kW at 85 %, 93 %, 720 h

Results

Energy used73,045kWh
Energy cost (your currency)657,406
Electrical input power101.45kW

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: 2 feed pumps of 90 kW at 80 % load, 94 % motor, 24 h. The inputs, in the units selected above:

InputValue
Motors running2.0000 -
Motor rated output90.000 kW
Load, share of rated output80.000 %
Motor efficiency at that load94.000 %
Running hours24.000 h
Electricity price per kWh (your currency)8.0000 -

Applying the formula below gives:

ResultValue
Energy used3,676.6 kWh
Energy cost (your currency)29,413
Electrical input power153.19 kW

Open this example in the calculator and change any input.

Formula

\(P_{in} = \frac{n\,P_r\,\lambda}{\eta_m} \qquad E = P_{in}\,t \qquad C = E\,c_e\)

Variables

Symbol Meaning SI unit
\(n\) motors running –
\(P_r\) motor rated output W
\(\lambda\) load, share of rated output –
\(\eta_m\) motor efficiency at that load –
\(t\) running hours s
\(c_e\) electricity price per kWh –
\(E\) energy used J
\(C\) energy cost –
\(P_{in}\) electrical input power W

Method and standards

Input power from the shaft output and the motor efficiency; energy over the running hours, shown in kWh.

Where it is used

  • Auxiliary power budgets of boiler houses.
  • Energy audits of pumps, fans and compressors.
  • Valuing efficient motors and variable speed drives.

Common mistakes

  • Using the nameplate rating as the actual load.
  • Using full-load efficiency at part load.
  • Forgetting drive (VFD, belt, gearbox) losses.

Assumptions and limits

  • Constant load over the period; efficiency at that load.

References

  • Electrical energy = input power x time (definition)

Questions and answers

How much energy does a motor use?

Output power times load over efficiency, times hours. Two 90 kW feed pump motors at 80 % load and 94 % efficiency draw 153 kW: 3677 kWh a day, about 29 400 at 8 per kWh.

Why divide by motor efficiency?

The rating is the shaft output; the meter sees the input, which includes the motor's losses.

How do I find the load?

Measure the input kW with a power analyser, or estimate from current, voltage and power factor; nameplate current alone overstates the load.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.