Worked example
Example: 2 feed pumps of 90 kW at 80 % load, 94 % motor, 24 h. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Motors running | 2.0000 - |
| Motor rated output | 90.000 kW |
| Load, share of rated output | 80.000 % |
| Motor efficiency at that load | 94.000 % |
| Running hours | 24.000 h |
| Electricity price per kWh (your currency) | 8.0000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Energy used | 3,676.6 kWh |
| Energy cost (your currency) | 29,413 |
| Electrical input power | 153.19 kW |
Open this example in the calculator and change any input.
Formula
\(P_{in} = \frac{n\,P_r\,\lambda}{\eta_m} \qquad E = P_{in}\,t \qquad C = E\,c_e\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(n\) | motors running | – |
| \(P_r\) | motor rated output | W |
| \(\lambda\) | load, share of rated output | – |
| \(\eta_m\) | motor efficiency at that load | – |
| \(t\) | running hours | s |
| \(c_e\) | electricity price per kWh | – |
| \(E\) | energy used | J |
| \(C\) | energy cost | – |
| \(P_{in}\) | electrical input power | W |
Method and standards
Input power from the shaft output and the motor efficiency; energy over the running hours, shown in kWh.
Where it is used
- Auxiliary power budgets of boiler houses.
- Energy audits of pumps, fans and compressors.
- Valuing efficient motors and variable speed drives.
Common mistakes
- Using the nameplate rating as the actual load.
- Using full-load efficiency at part load.
- Forgetting drive (VFD, belt, gearbox) losses.
Assumptions and limits
- Constant load over the period; efficiency at that load.
References
- Electrical energy = input power x time (definition)
Questions and answers
How much energy does a motor use?
Output power times load over efficiency, times hours. Two 90 kW feed pump motors at 80 % load and 94 % efficiency draw 153 kW: 3677 kWh a day, about 29 400 at 8 per kWh.
Why divide by motor efficiency?
The rating is the shaft output; the meter sees the input, which includes the motor's losses.
How do I find the load?
Measure the input kW with a power analyser, or estimate from current, voltage and power factor; nameplate current alone overstates the load.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.