FireCADCalc

Current-Sense Shunt Resistor and Amplifier Gain

Shunt resistance, power and voltage drop for measuring a current, and the amplifier gain to scale the shunt voltage to an ADC full scale.

Inputs

Examples: Illustrative: 20 A, 50 mV shunt, 3.3 V 12-bit ADC, 7.5 A nowBattery monitor 100 A, 75 mV shunt, 16-bit 2.048 V ADC, 42 ALow current 500 mA, 100 mV, 5 V 10-bit, 120 mA

Accepted: 1E-6 to 5,000 A
Accepted: 1 to 1,000 mV
Accepted: 0.1 to 10 V
Accepted: 8 to 24
Accepted: 0 to 5,000 A

Results

R = V_sh/I_max. 50–100 mV full scale balances accuracy against loss; choose a shunt rated for at least twice the power and use a Kelvin (four-terminal) connection. Low-side shunts are simpler; high-side needs a current-sense amplifier.

Shunt resistance0.75000mΩ
Shunt power at full current7.5000W
Amplifier gain to reach ADC full scale27.307
Current per ADC count1.5259mA
ADC input at the present current0.86016V
ADC counts at the present current27,525

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Illustrative: 20 A, 50 mV shunt, 3.3 V 12-bit ADC, 7.5 A now. The inputs, in the units selected above:

InputValue
Maximum current to measure20.000 A
Shunt voltage at full scale50.000 mV
ADC full-scale input3.3000 V
ADC resolution (bits)12.000 -
Present current7.5000 A

Applying the formula below gives:

ResultValue
Shunt resistance2.5000 mΩ
Shunt power at full current1.0000 W
Amplifier gain to reach ADC full scale66.000
Current per ADC count4.8828 mA
ADC input at the present current1.2375 V
ADC counts at the present current1,535.0

Open this example in the calculator and change any input.

Formula

\(R_{sh} = \frac{V_{sh,max}}{I_{max}}, \quad P = I_{max}^2R_{sh}, \quad G = \frac{V_{FS}}{V_{sh,max}}, \quad I_{LSB} = \frac{I_{max}}{2^n}\)

Variables

Symbol Meaning SI unit
\(I_{max}\) Maximum current to measure A
\(V_{sh,max}\) Shunt voltage at full scale V
\(V_{FS}\) ADC full-scale input V
\(n\) ADC resolution (bits) -
\(I\) Present current A
\(R_{sh}\) Shunt resistance Ω
\(P_{max}\) Shunt power at full current W
\(G\) Amplifier gain to reach ADC full scale -
\(I_{LSB}\) Current per ADC count A
\(V_{ADC}\) ADC input at the present current V
\(N\) ADC counts at the present current -

Method and standards

Shunt measurement scaling.

Where it is used

  • Battery management, motor drives and power monitors.
  • DC panel meters and data loggers.

Common mistakes

  • Forgetting the shunt temperature rise and its tempco.
  • Measuring across the leads instead of the Kelvin terminals.

Assumptions and limits

  • Ideal amplifier; linear ADC.

References

  • Shunt current measurement and ADC scaling

Questions and answers

Why not use a bigger shunt voltage?

A bigger drop improves accuracy against offsets but wastes power and heats the shunt; 50–100 mV is the usual compromise.

What is a Kelvin connection?

Separate sense wires taken from the shunt's own terminals so the drop in the current-carrying leads and solder joints is not measured.

What do the defaults represent?

An illustrative 20 A full-scale measurement with a 50 mV shunt into a 3.3 V, 12-bit ADC, now reading 7.5 A.

Method and article reviewed by FireCAD engineering on 17 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Sources

Horowitz and Hill, The Art of Electronics, 3rd ed. (Cambridge University Press, 2015), ch. 9

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.