Worked example
Example: 12 bit, 10 V, 200 °C span, 3.3 V in, SINAD 68 dB. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Resolution in bits | 12.000 - |
| Full-scale input range | 10.000 V |
| Engineering span represented by full scale | 200.00 - |
| Input voltage to convert to counts | 3.3000 V |
| Measured SINAD for ENOB (dB) | 68.000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| LSB in volts V_FS / 2ᴺ | 2.4414 mV |
| LSB in engineering units | 0.048828 |
| Counts for the input voltage (rounded down) | 1,351.0 |
| Ideal quantisation SNR 6.02 N + 1.76 (dB) | 74.000 |
| Effective number of bits for the SINAD | 11.003 |
Open this example in the calculator and change any input.
Formula
\(q = \frac{V_{FS}}{2^N}, \quad SNR = 6.02N + 1.76\ \text{dB}, \quad ENOB = \frac{SINAD - 1.76}{6.02}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(N\) | Resolution in bits | - |
| \(V_{FS}\) | Full-scale input range | V |
| \(S\) | Engineering span represented by full scale | - |
| \(V\) | Input voltage to convert to counts | V |
| \(SINAD\) | Measured SINAD for ENOB (dB) | - |
| \(q\) | LSB in volts V_FS / 2ᴺ | V |
| \(q_{EU}\) | LSB in engineering units | - |
| \(n\) | Counts for the input voltage (rounded down) | - |
| \(SNR\) | Ideal quantisation SNR 6.02 N + 1.76 (dB) | - |
| \(ENOB\) | Effective number of bits for the SINAD | - |
Method and standards
Uniform quantisation.
Where it is used
- PLC and DCS input resolution checks.
- Data acquisition design.
Common mistakes
- Counting the sign bit for unipolar ranges.
- Expecting the ideal SNR in practice.
Assumptions and limits
- Uniform, unipolar converter.
References
- Ideal quantisation of an N-bit converter; SNR = 6.02 N + 1.76 dB for a full-scale sine (IEEE 1241)
Questions and answers
What is the step of a 12-bit, 10 V converter?
2.44 mV; over a 200 °C span, 0.049 °C.
What SNR can 12 bits give?
74 dB in theory.
What is ENOB?
The bits a real converter delivers: (SINAD − 1.76)/6.02; 68 dB is 11 bits.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.