Worked example
Example: Quarter bridge, 500 µε, 5 V. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Gauge factor | 2.0000 - |
| Strain | 5.0000e-04 - |
| Excitation voltage | 5.0000 V |
| Arrangement | Quarter bridge (one active gauge) |
Applying the formula below gives:
| Result | Value |
|---|---|
| Bridge output | 1.2494 mV |
| Linear approximation | 1.2500 mV |
| Non-linearity (exact vs linear) | -0.049975 % |
Open this example in the calculator and change any input.
Formula
\(V_o = V_{ex}\,\frac{GF\,\varepsilon/4}{1 + GF\,\varepsilon/2}\ (\tfrac14), \quad V_o = V_{ex}\,\frac{GF\,\varepsilon}{2}\ (\tfrac12), \quad V_o = V_{ex}\, GF\,\varepsilon\ (\text{full})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(GF\) | Gauge factor | - |
| \(\varepsilon\) | Strain | - |
| \(V_{ex}\) | Excitation voltage | V |
| \(\text{bridge}\) | Arrangement | - |
| \(V_o\) | Bridge output | V |
| \(V_{lin}\) | Linear approximation | V |
| \(e_{nl}\) | Non-linearity (exact vs linear) | - |
Method and standards
Bridge equations.
Where it is used
- Stress measurement on structures.
- Load cell and torque sensor design.
Common mistakes
- Microstrain entered as strain.
- Lead resistance ignored.
Assumptions and limits
- Equal arms, ideal bridge.
- Half and full bridge outputs assume the active gauges see equal and opposite strain, as in bending. With axial loading and Poisson gauges the output is smaller: \(GF\,\varepsilon(1+\nu)/4 \times V_{ex}\) for a half bridge and \(GF\,\varepsilon(1+\nu)/2 \times V_{ex}\) for a full bridge.
References
- Wheatstone bridge with strain gauges
- ΔR/R = GF ε
Questions and answers
What does 500 µε give in a quarter bridge at 5 V, GF 2?
1.2494 mV (linear 1.25 mV).
And a full bridge?
5 mV, four times more.
Why is the quarter bridge non-linear?
Only one arm changes, so the bridge current changes too.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.