Worked example
Example: 50,000 h MTBF, 8 h MTTR, two units, one year. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Mean time between failures | 50,000 h |
| Mean time to repair | 8.0000 h |
| Number of identical items | 2.0000 - |
| Mission time | 8,760.0 h |
Applying the formula below gives:
| Result | Value |
|---|---|
| Availability of one item | 99.984 % |
| Availability, n in series | 99.968 % |
| Availability, n in parallel (1 needed) | 100.000 % |
| Reliability of one item over the mission | 83.929 % |
| Expected downtime per year, one item | 1.4014 h |
Open this example in the calculator and change any input.
Formula
\(A = \frac{MTBF}{MTBF + MTTR}, \quad A_s = A^n, \quad A_p = 1 - (1 - A)^n, \quad R(t) = e^{-t/MTBF}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(MTBF\) | Mean time between failures | s |
| \(MTTR\) | Mean time to repair | s |
| \(n\) | Number of identical items | - |
| \(t\) | Mission time | s |
| \(A\) | Availability of one item | - |
| \(A_s\) | Availability, n in series | - |
| \(A_p\) | Availability, n in parallel (1 needed) | - |
| \(R(t)\) | Reliability of one item over the mission | - |
| \(D\) | Expected downtime per year, one item | s |
Method and standards
Constant-failure-rate reliability.
Where it is used
- Pump and fan redundancy decisions.
- Instrument system availability.
Common mistakes
- Ignoring common-cause failures.
- Using MTBF for wear-out items.
Assumptions and limits
- Independent, constant failure rates.
- The number of items is a whole number; a fractional entry is rounded, with a note.
References
- Reliability mathematics with constant failure rates (definitions; O'Connor, Practical Reliability Engineering)
Questions and answers
Why does redundancy help so much?
With two pumps each 99 % available, both are down at once only 0.01 % of the time.
Why does series hurt?
Every item must work; ten items each 99 % available give only 90 %.
What do the defaults represent?
Items with 50,000 h MTBF and 8 h repair, two in parallel, over one year.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.