Worked example
Example: 10 kΩ, 1 µF against 50 Hz. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Resistance | 10,000 Ω |
| Capacitance | 1.0000 µF |
| Signal or noise frequency | 50.000 Hz |
Applying the formula below gives:
| Result | Value |
|---|---|
| Cut-off frequency (−3 dB) | 15.915 Hz |
| Time constant | 0.010000 s |
| Gain at f | 0.30331 |
| Attenuation at f (dB) | 10.362 |
| Phase lag at f | 72.343 ° |
Open this example in the calculator and change any input.
Formula
\(f_c = \frac{1}{2\pi RC}, \quad |G| = \frac{1}{\sqrt{1 + (f/f_c)^2}}, \quad \phi = \arctan\frac{f}{f_c}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(R\) | Resistance | Ω |
| \(C\) | Capacitance | F |
| \(f\) | Signal or noise frequency | 1/s |
| \(f_c\) | Cut-off frequency (−3 dB) | 1/s |
| \(\tau\) | Time constant | s |
| \(|G|\) | Gain at f | - |
| \(A\) | Attenuation at f (dB) | - |
| \(\phi\) | Phase lag at f | rad |
Method and standards
First-order response.
Where it is used
- Signal conditioning and noise filtering.
- Choosing transmitter damping.
Common mistakes
- Filtering more than needed.
- Ignoring loading by the next stage.
Assumptions and limits
- Unloaded first-order RC.
References
- First-order RC low-pass filter (circuit theory definitions)
Questions and answers
How much does a filter attenuate 50 Hz pickup?
A 0.01 s time constant (16 Hz cut-off) cuts 50 Hz by about 10 dB, a factor of three.
Why not filter heavily?
Filtering adds lag to the measurement and can destabilise or slow a control loop.
What do the defaults represent?
A 10 kΩ, 1 µF filter facing 50 Hz noise.
Method and article reviewed by FireCAD engineering on 13 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.