Worked example
Example: Bare thermocouple, 10 s: 100 K step, after 30 s, 5 K/min ramp. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Time constant of the sensor | 10.000 s |
| Size of the step change | 100.00 K |
| Time after the step | 30.000 s |
| Rate of a steady ramp | 5.0000 °C/min |
Applying the formula below gives:
| Result | Value |
|---|---|
| Share of the step shown at time t: 1 − e^(−t/τ) | 95.021 % |
| Change shown by the sensor at time t | 95.021 K |
| Error left at time t | 4.9787 K |
| Time to 90 % of the step | 23.026 s |
| Time to 95 % | 29.957 s |
| Time to 99 % | 46.052 s |
| Steady lag behind a ramp r τ | 0.83333 K |
Open this example in the calculator and change any input.
Formula
\(f = 1 - e^{-t/\tau}, \quad t_x = -\tau \ln(1 - x)\)
\(e_r = r\,\tau\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\tau\) | Time constant of the sensor | s |
| \(\Delta T\) | Size of the step change | K |
| \(t\) | Time after the step | s |
| \(r\) | Rate of a steady ramp | K/s |
| \(f\) | Share of the step shown at time t: 1 − e^(−t/τ) | - |
| \(\Delta T_r\) | Change shown by the sensor at time t | K |
| \(e\) | Error left at time t | K |
| \(t_{90}\) | Time to 90 % of the step | s |
| \(t_{95}\) | Time to 95 % | s |
| \(t_{99}\) | Time to 99 % | s |
| \(e_r\) | Steady lag behind a ramp r τ | K |
Method and standards
Solution of the first-order equation τ dT_s/dt + T_s = T for a step and a ramp.
Where it is used
- Choosing sensors for fast loops.
- Explaining reading lag during boiler start-up.
- Control loop tuning.
Common mistakes
- Confusing the time constant with the 99 % time.
- Testing in still air and using the value in flowing water.
Assumptions and limits
- First-order response.
References
- First-order system step and ramp response (control theory)
Questions and answers
How long does a 10 s sensor take to show 99 % of a step?
46 s (4.6 time constants). After 30 s it shows 95 %.
How far behind a 5 °C/min ramp does it read?
0.83 °C: the rate times the time constant.
Why is a thermowell slower?
The extra mass and air gap add lag; time constants of a minute or more are common.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.