Worked example
Example: Type K at 400 °C, cold junction 25 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Thermocouple type | Type K (Chromel / Alumel) |
| Measuring (hot) junction temperature | 400.00 °C |
| Reference (cold) junction temperature | 25.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| EMF at the instrument terminals | 15.397 mV |
| EMF with the cold junction at 0 °C (table value) | 16.397 mV |
| EMF of the cold junction temperature (vs 0 °C) | 1.0002 mV |
| Sensitivity at the hot junction | 42.241 µV/K |
Open this example in the calculator and change any input.
Formula
\(E = E(T) - E(T_{ref})\)
\(E(t) = \sum_{i=0}^{n} c_i\, t^{i} \;\; \left(+\, a_0\, e^{a_1 (t - a_2)^2}\ \text{for type K above 0 °C}\right)\)
\(S = \frac{dE}{dT}\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{type}\) | thermocouple type (letter designation) | - |
| \(T\) | measuring (hot) junction temperature | K |
| \(T_{ref}\) | reference (cold) junction temperature | K |
| \(E\) | EMF at the instrument terminals | V |
| \(E(T)\) | EMF with the cold junction at 0 °C (table value) | V |
| \(E(T_{ref})\) | EMF corresponding to the cold junction temperature | V |
| \(S\) | sensitivity (Seebeck coefficient of the pair) at T | V/K |
| \(t\) | temperature in °C used inside the reference function | °C |
| \(c_i, a_0, a_1, a_2\) | NIST reference-function coefficients for each type and subrange | mV, °C |
Method and standards
The EMF comes from the ITS-90 thermocouple reference functions published by NIST (Monograph 175, Standard Reference Database 60), the same functions on which IEC 60584-1 and ASTM E230 tables are based. Each type has one to three temperature subranges with its own polynomial; type K above 0 °C adds an exponential term. The coefficients are read from NIST's published files, and the result is checked against every point of NIST's printed tables. The sensitivity is the exact derivative of the function.
Where it is used
- Checking a thermocouple input card or transmitter with a mV source.
- Finding what a temperature should read at the panel when the terminals are warm.
- Comparing thermocouple types for resolution at the working temperature.
Common mistakes
- Simulating a temperature with the table mV while the terminals are not at 0 °C: subtract the cold-junction EMF.
- Using the wrong type: a type J table on a type K sensor reads far off at high temperature.
- Treating the sensitivity as constant over a wide range; the curve is not straight, especially for B, R, S and below 0 °C.
Assumptions and limits
- Reference functions for standard thermocouple wire; real sensors carry the tolerance class of their wire (not included).
- Ranges: B 0–1 820 °C, E −270–1 000 °C, J −210–1 200 °C, K −270–1 372 °C, N −270–1 300 °C, R and S −50–1 768.1 °C, T −270–400 °C.
- Extension and compensating cables are assumed to match the thermocouple up to the terminals.
References
- NIST Monograph 175 / SRD 60 ITS-90 reference functions (as adopted in IEC 60584-1 and ASTM E230)
Questions and answers
What mV does a type K thermocouple give at 400 °C?
16.397 mV with the cold junction at 0 °C. With the instrument terminals at 25 °C the meter reads 15.397 mV, because 25 °C itself is worth 1.000 mV.
How sensitive is a type K thermocouple?
About 41–42 µV per °C over most of its range; type J about 55 µV/°C at 300 °C; type S only about 12 µV/°C at 1 000 °C.
Why does the cold junction matter?
A thermocouple measures the difference between its two junctions. The EMF at the terminals is E(T) − E(T_ref), so the terminal temperature must be known or compensated.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.