RTD Self-Heating Error

Temperature error of a resistance thermometer heated by its own measuring current, from the current, resistance and self-heating coefficient.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliser

Inputs

Examples: Pt100 at 100 °C, 1 mA, 2 mW/KSame at 5 mAPt1000 at 0 °C, 0.3 mA, 8 mW/K in flowing water

In mW per K, from the sensor data sheet, for the medium and flow it sits in (still air is far lower than flowing water). If the data sheet gives K/mW (°C/mW), enter its reciprocal.

Results

Power in the sensor I² R0.13850mW
Self-heating error (reads high)0.069250K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Pt100 at 100 °C, 1 mA, 2 mW/K. The inputs, in the units selected above:

InputValue
Measuring current1.0000 mA
Sensor resistance at the temperature138.50 Ω
Self-heating coefficient (mW per K)2.0000 -

Applying the formula below gives:

ResultValue
Power in the sensor I² R0.13850 mW
Self-heating error (reads high)0.069250 K

Open this example in the calculator and change any input.

Formula

\(P = I^2 R, \quad \Delta T = \frac{P}{k_{sh}}\)

Variables

Symbol Meaning SI unit
\(I\) Measuring current A
\(R\) Sensor resistance at the temperature Ω
\(k_{sh}\) Self-heating coefficient (mW per K) -
\(P\) Power in the sensor I² R W
\(\Delta T\) Self-heating error (reads high) K

Method and standards

Power balance at the sensor.

Where it is used

  • Choosing excitation current.
  • Precision temperature checks.

Common mistakes

  • Coefficient for the wrong medium.
  • High currents for better signal.

Assumptions and limits

  • Steady state.
  • k_sh is in mW per K. Some data sheets give the inverse, a self-heating error in K/mW (°C/mW): enter 1 divided by that value.

References

  • ΔT = I² R / k (IEC 60751 self-heating definition)

Questions and answers

1 mA through a Pt100 at 100 °C with 2 mW/K?

0.1385 mW, error 0.069 K.

And at 5 mA?

25 times more: about 1.7 K.

Why does the medium matter?

Flowing liquid carries heat away; still air does not.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.