Worked example
Example: Pt100 at 200 °C, 2-wire, 100 m of 13 Ω/km. The inputs, in the units selected above:
| Input | Value |
|---|---|
| RTD resistance at 0 °C (100 or 1000) | 100.00 Ω |
| Measured temperature | 200.00 °C |
| Connection | 2-wire |
| Resistance of one conductor per km | 13.000 Ω/km |
| Cable length, sensor to instrument (one way) | 100.00 m |
| Mismatch between the leads, 3-wire (share of one lead) | 5.0000 % |
Applying the formula below gives:
| Result | Value |
|---|---|
| Resistance of one lead | 1.3000 Ω |
| Resistance added to the reading | 2.6000 Ω |
| RTD sensitivity at the temperature (Ω per K) | 0.36773 |
| Temperature error (reads high) | 7.0704 K |
Open this example in the calculator and change any input.
Formula
\(R_L = r L\)
\(\Delta R = 2 R_L \ \text{(2-wire)}, \; m R_L \ \text{(3-wire)}, \; 0 \ \text{(4-wire)}\)
\(\Delta T = \frac{\Delta R}{dR/dT}, \quad dR/dT = R_0 \left[A + 2 B t + C\,(4t^3 - 300t^2)\right]\ \ (C = 0\ \text{for}\ t \ge 0\ ^\circ\mathrm{C})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(R_0\) | resistance at 0 °C | Ω |
| \(T\) | measured temperature | K |
| \(t\) | temperature in °C | °C |
| \(\text{wiring}\) | connection | - |
| \(r\) | resistance of one conductor per km | Ω/m |
| \(L\) | cable length, one way | m |
| \(m\) | lead mismatch (3-wire) | - |
| \(A, B, C\) | IEC 60751 coefficients | 1/°C, 1/°C², 1/°C⁴ |
| \(R_L\) | resistance of one lead | Ω |
| \(\Delta R\) | added resistance | Ω |
| \(dR/dT\) | sensitivity | Ω/K |
| \(\Delta T\) | temperature error | K |
Method and standards
The added resistance of the leads reads as extra temperature; dividing by the RTD's sensitivity (the slope of the IEC 60751 curve, with the C term below 0 °C) gives the error.
Where it is used
- Choosing 2, 3 or 4-wire connection.
- Explaining a high RTD reading on a long run.
- Specifying cable size for RTD circuits.
Common mistakes
- Using 2-wire on long cable runs.
- Mixing conductor sizes in a 3-wire circuit.
- Forgetting terminal and junction resistance.
Assumptions and limits
- Steady current; cable resistance at its actual temperature.
- The sensitivity dR/dT is shown in Ω per K in every unit system.
References
- IEC 60751 Callendar–Van Dusen slope
Questions and answers
How much error does 100 m of cable add to a 2-wire Pt100?
With 13 Ω/km per conductor, 2.6 Ω in the loop: about 7 °C high at 200 °C.
How good is 3-wire?
It cancels matched leads; with a 5 % mismatch the error falls to about 0.2 °C in the same case.
When use 4-wire?
For precise measurements or long runs: the current and sense leads are separate, so lead resistance does not enter.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.