RTD Lead Wire Error: 2-Wire, 3-Wire and 4-Wire

Temperature error that lead wire resistance adds to a Pt100 or Pt1000 reading in 2-wire, 3-wire and 4-wire connections, from cable length and resistance.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserBoiler

Inputs

Examples: Pt100 at 200 °C, 2-wire, 100 m of 13 Ω/kmSame, 3-wire with 5 % mismatchPt100 at -50 °C, 2-wire, 30 m of 36 Ω/km

From the cable data sheet at the cable's temperature.

Results

Lead resistance also changes with cable temperature; 3-wire cancels only matched leads, 4-wire cancels them fully.

Resistance of one lead1.3000Ω
Resistance added to the reading2.6000Ω
RTD sensitivity at the temperature (Ω per K)0.36773
Temperature error (reads high)7.0704K

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Pt100 at 200 °C, 2-wire, 100 m of 13 Ω/km. The inputs, in the units selected above:

InputValue
RTD resistance at 0 °C (100 or 1000)100.00 Ω
Measured temperature200.00 °C
Connection2-wire
Resistance of one conductor per km13.000 Ω/km
Cable length, sensor to instrument (one way)100.00 m
Mismatch between the leads, 3-wire (share of one lead)5.0000 %

Applying the formula below gives:

ResultValue
Resistance of one lead1.3000 Ω
Resistance added to the reading2.6000 Ω
RTD sensitivity at the temperature (Ω per K)0.36773
Temperature error (reads high)7.0704 K

Open this example in the calculator and change any input.

Formula

\(R_L = r L\)

\(\Delta R = 2 R_L \ \text{(2-wire)}, \; m R_L \ \text{(3-wire)}, \; 0 \ \text{(4-wire)}\)

\(\Delta T = \frac{\Delta R}{dR/dT}, \quad dR/dT = R_0 \left[A + 2 B t + C\,(4t^3 - 300t^2)\right]\ \ (C = 0\ \text{for}\ t \ge 0\ ^\circ\mathrm{C})\)

Variables

Symbol Meaning SI unit
\(R_0\) resistance at 0 °C Ω
\(T\) measured temperature K
\(t\) temperature in °C °C
\(\text{wiring}\) connection -
\(r\) resistance of one conductor per km Ω/m
\(L\) cable length, one way m
\(m\) lead mismatch (3-wire) -
\(A, B, C\) IEC 60751 coefficients 1/°C, 1/°C², 1/°C⁴
\(R_L\) resistance of one lead Ω
\(\Delta R\) added resistance Ω
\(dR/dT\) sensitivity Ω/K
\(\Delta T\) temperature error K

Method and standards

The added resistance of the leads reads as extra temperature; dividing by the RTD's sensitivity (the slope of the IEC 60751 curve, with the C term below 0 °C) gives the error.

Where it is used

  • Choosing 2, 3 or 4-wire connection.
  • Explaining a high RTD reading on a long run.
  • Specifying cable size for RTD circuits.

Common mistakes

  • Using 2-wire on long cable runs.
  • Mixing conductor sizes in a 3-wire circuit.
  • Forgetting terminal and junction resistance.

Assumptions and limits

  • Steady current; cable resistance at its actual temperature.
  • The sensitivity dR/dT is shown in Ω per K in every unit system.

References

  • IEC 60751 Callendar–Van Dusen slope

Questions and answers

How much error does 100 m of cable add to a 2-wire Pt100?

With 13 Ω/km per conductor, 2.6 Ω in the loop: about 7 °C high at 200 °C.

How good is 3-wire?

It cancels matched leads; with a 5 % mismatch the error falls to about 0.2 °C in the same case.

When use 4-wire?

For precise measurements or long runs: the current and sense leads are separate, so lead resistance does not enter.

Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.