Worked example
Example: Type K reading 15.000 mV, terminals at 25 °C. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Thermocouple type | Type K (Chromel / Alumel) |
| Measured EMF at the terminals | 15.000 mV |
| Cold junction (terminal) temperature | 25.000 °C |
Applying the formula below gives:
| Result | Value |
|---|---|
| Hot junction temperature | 390.60 °C |
| EMF added for the cold junction | 1.0002 mV |
| Compensated EMF (vs 0 °C) | 16.000 mV |
| Reading without cold junction compensation | 366.84 °C |
| Error if the compensation is left out | 23.755 K |
Open this example in the calculator and change any input.
Formula
\(E(T) = E_m + E(T_{cj})\)
\(T = E^{-1}\!\left(E_m + E(T_{cj})\right)\)
\(\Delta T = T - E^{-1}(E_m) = T - T_u\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(\text{type}\) | thermocouple type (letter designation) | - |
| \(E_m\) | EMF measured at the terminals | V |
| \(T_{cj}\) | cold junction (terminal) temperature | K |
| \(E(T_{cj})\) | EMF corresponding to the cold junction temperature | V |
| \(E(T)\) | compensated EMF, referred to 0 °C | V |
| \(T\) | hot junction temperature | K |
| \(T_u\) | temperature read if no compensation is applied | K |
| \(\Delta T\) | error when the compensation is left out | K |
| \(E^{-1}\) | inverse of the NIST reference function, solved numerically | - |
Method and standards
Cold-junction compensation adds the EMF of the terminal temperature to the measured EMF, then converts the total to temperature through the ITS-90 reference function of NIST Monograph 175 (SRD 60). The conversion solves the reference function itself rather than NIST's approximate inverse polynomials, so it carries no extra error (NIST's inverses are good to about ±0.05 °C). Type B is inverted only from 50 °C, as its EMF is not single-valued below about 42 °C.
Where it is used
- Checking a temperature reading with a millivoltmeter at the junction box or panel.
- Verifying the cold-junction compensation of a transmitter or input card.
- Troubleshooting a reading that is off by about the panel temperature.
Common mistakes
- Adding the terminal temperature in °C instead of its EMF in mV.
- Taking the cold junction as the ambient temperature when the terminals sit in a warm panel or junction box.
- Reversed polarity: a negative mV reading at a hot process usually means the leads are crossed.
Assumptions and limits
- Reference functions for standard thermocouple wire; sensor tolerance class not included.
- The cold junction temperature is that of the point where the thermocouple or matching extension cable ends on copper.
- The measured EMF is assumed free of noise, lead-voltage drop and ground loops.
References
- NIST Monograph 175 / SRD 60 ITS-90 reference functions (as adopted in IEC 60584-1 and ASTM E230)
Questions and answers
A type K thermocouple reads 15.000 mV with its terminals at 25 °C. What is the temperature?
390.6 °C. Adding the 1.000 mV of the 25 °C terminals gives 16.000 mV, which is 390.6 °C on the type K function.
How big is the error if the cold junction is ignored?
In the example above the uncompensated reading is 366.8 °C, about 24 °C low: roughly the terminal temperature, scaled by the ratio of sensitivities.
Why not just add the terminal temperature to the reading?
Because the thermocouple curve is not straight. Compensation must be done in mV: add E(T_cj), then convert the total to temperature.
Method and article reviewed by FireCAD engineering on 12 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.