Worked example
Example: Pt100 at 200 °C; reading 138.51 Ω. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Resistance at 0 °C (100 for Pt100, 1000 for Pt1000) | 100.00 Ω |
| Temperature | 200.00 °C |
| Measured resistance | 138.51 Ω |
Applying the formula below gives:
| Result | Value |
|---|---|
| Resistance at the temperature | 175.86 Ω |
| Temperature for the measured resistance | 100.01 °C |
Open this example in the calculator and change any input.
Formula
\(R(t) = R_0\left[1 + A t + B t^2 + C (t - 100)\,t^3\right] \quad (C = 0\ \text{for}\ t \ge 0\ ^\circ\mathrm{C})\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(R_0\) | resistance at 0 °C | Ω |
| \(T\) | temperature | K |
| \(R_m\) | measured resistance | Ω |
| \(R_T\) | resistance at T | Ω |
| \(T_m\) | temperature for R_m | K |
| \(t\) | temperature in °C | °C |
| \(A, B, C\) | IEC 60751 coefficients: 3.9083×10⁻³, −5.775×10⁻⁷, −4.183×10⁻¹² | 1/°C, 1/°C², 1/°C⁴ |
Method and standards
IEC 60751 Callendar–Van Dusen equation for industrial platinum resistance thermometers (α = 0.00385); the inverse is solved numerically.
Where it is used
- Checking RTD readings with a multimeter.
- Configuring transmitters.
- Troubleshooting temperature loops.
Common mistakes
- Using Pt100 values for Pt1000 sensors.
- Ignoring lead resistance in 2-wire circuits.
- Using the formula outside −200 to 850 °C.
Assumptions and limits
- IEC 60751 standard curve; sensor tolerance class not included.
- The two directions are independent: a measured resistance outside the −200 °C to 850 °C range leaves out only its temperature, with a note.
References
- IEC 60751 Callendar–Van Dusen coefficients A
- B
- C
Questions and answers
What resistance does a Pt100 have at 200 °C?
175.86 Ω. A Pt100 reading 138.51 Ω is at 100.0 °C.
Why does the formula change below 0 °C?
IEC 60751 adds the C term only below 0 °C to fit the platinum curve at low temperatures.
How much error do the leads add?
A Pt100 changes about 0.385 Ω per K, so each ohm of lead resistance reads about 2.6 K high in a 2-wire connection; 3- or 4-wire connections cancel it.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.