4–20 mA Signal Scaling Calculator

Converts a 4–20 mA signal to engineering units and back, for linear transmitters and square-root (DP flow) signals, from the range values.

Thermal power plantProcess steam and utilitiesRefinery and petrochemicalChemical and fertiliserBoiler

Inputs

Examples: Pressure 0-16 bar at 12 mA; 10 bar is?Temperature 0-400 °C at 7.2 mA; 300 °C is?DP flow 0-50 t/h, square root, at 8 mA; 40 t/h is?

Results

Process value at the signal8.0000
Share of range50.000%
Signal for the value to convert14.000mA

Download PDF CSV Link to this result Compare another case

Log in to save calculations to your dashboard.

Worked example

Example: Pressure 0-16 bar at 12 mA; 10 bar is?. The inputs, in the units selected above:

InputValue
Signal current12.000 mA
Value at 4 mA (any unit)0 -
Value at 20 mA (same unit)16.000 -
Signal lawLinear
Value to convert to mA (same unit)10.000 -

Applying the formula below gives:

ResultValue
Process value at the signal8.0000
Share of range50.000 %
Signal for the value to convert14.000 mA

Open this example in the calculator and change any input.

Formula

\(f = \frac{I - 4\ \mathrm{mA}}{16\ \mathrm{mA}} \qquad PV = LRV + (URV - LRV)\,f \ \ (\text{or}\ \sqrt{f}) \qquad I_x = 4\ \mathrm{mA} + 16\ \mathrm{mA}\cdot\frac{x - LRV}{URV - LRV}\ \ (\text{squared for}\ \sqrt{\ })\)

Variables

Symbol Meaning SI unit
\(I\) signal current A
\(LRV\) value at 4 mA any
\(URV\) value at 20 mA any
\(\text{law}\) linear or square root –
\(x\) value to convert any
\(PV\) process value any
\(f\) share of range –
\(I_x\) signal for the value A

Method and standards

Linear scaling of the 4–20 mA live-zero signal; square-root extraction for differential-pressure flow.

Where it is used

  • Commissioning and loop checks.
  • Configuring DCS and PLC inputs.
  • Troubleshooting readings.

Common mistakes

  • Extracting square root twice (transmitter and DCS).
  • Scaling 0–20 instead of 4–20 mA.
  • Ignoring the low-flow cut-off on square-root signals.

Assumptions and limits

  • Ideal linear transmitter; no damping or saturation limits.
  • The 3.8–20.5 mA band used for the warning is the measuring range of NAMUR NE 43; transmitters that do not follow NE 43 may saturate or signal faults at other levels.

References

  • Live-zero 4–20 mA signal (IEC 60381-1); NAMUR NE 43 (signal levels for failure information)

Questions and answers

What does 12 mA mean on a 0–16 bar transmitter?

Half range: 8 bar. And 10 bar should read 14 mA.

How is a DP flow signal scaled?

Flow goes with the square root of DP: at 8 mA (25 % of DP) the flow is 50 % of range, 25 t/h on a 0–50 t/h meter.

What does 3.6 mA or 21 mA mean?

Outside the normal band: usually a sensor or wiring fault; many transmitters signal faults this way.

Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.

Related calculators

Free engineering calculators: every page computes in SI and converts to your units. Results are for engineering estimation; verify critical designs against the referenced standards.

Rejoining the server...

Rejoin failed... trying again in seconds.

Failed to rejoin.
Please retry or reload the page.

The session has been paused by the server.

Failed to resume the session.
Please retry or reload the page.