Worked example
Example: Pressure 0-16 bar at 12 mA; 10 bar is?. The inputs, in the units selected above:
| Input | Value |
|---|---|
| Signal current | 12.000 mA |
| Value at 4 mA (any unit) | 0 - |
| Value at 20 mA (same unit) | 16.000 - |
| Signal law | Linear |
| Value to convert to mA (same unit) | 10.000 - |
Applying the formula below gives:
| Result | Value |
|---|---|
| Process value at the signal | 8.0000 |
| Share of range | 50.000 % |
| Signal for the value to convert | 14.000 mA |
Open this example in the calculator and change any input.
Formula
\(f = \frac{I - 4\ \mathrm{mA}}{16\ \mathrm{mA}} \qquad PV = LRV + (URV - LRV)\,f \ \ (\text{or}\ \sqrt{f}) \qquad I_x = 4\ \mathrm{mA} + 16\ \mathrm{mA}\cdot\frac{x - LRV}{URV - LRV}\ \ (\text{squared for}\ \sqrt{\ })\)
Variables
| Symbol | Meaning | SI unit |
|---|---|---|
| \(I\) | signal current | A |
| \(LRV\) | value at 4 mA | any |
| \(URV\) | value at 20 mA | any |
| \(\text{law}\) | linear or square root | – |
| \(x\) | value to convert | any |
| \(PV\) | process value | any |
| \(f\) | share of range | – |
| \(I_x\) | signal for the value | A |
Method and standards
Linear scaling of the 4–20 mA live-zero signal; square-root extraction for differential-pressure flow.
Where it is used
- Commissioning and loop checks.
- Configuring DCS and PLC inputs.
- Troubleshooting readings.
Common mistakes
- Extracting square root twice (transmitter and DCS).
- Scaling 0–20 instead of 4–20 mA.
- Ignoring the low-flow cut-off on square-root signals.
Assumptions and limits
- Ideal linear transmitter; no damping or saturation limits.
- The 3.8–20.5 mA band used for the warning is the measuring range of NAMUR NE 43; transmitters that do not follow NE 43 may saturate or signal faults at other levels.
References
- Live-zero 4–20 mA signal (IEC 60381-1); NAMUR NE 43 (signal levels for failure information)
Questions and answers
What does 12 mA mean on a 0–16 bar transmitter?
Half range: 8 bar. And 10 bar should read 14 mA.
How is a DP flow signal scaled?
Flow goes with the square root of DP: at 8 mA (25 % of DP) the flow is 50 % of range, 25 t/h on a 0–50 t/h meter.
What does 3.6 mA or 21 mA mean?
Outside the normal band: usually a sensor or wiring fault; many transmitters signal faults this way.
Method and article reviewed by FireCAD engineering on 11 November 2026. Every result is checked against an independent calculation on each release: how we verify our calculators.